| Date |
Text |
| 2021-09-08 08:40:25 | 09/08/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A1.00, IT SHOWS A DIFFERENT LAYOUT FROM THE |
| | GENERAL FOOD SERVICE EQUIPMENT SERVICE, AND ONE HAS A |
| | FOUR-BURNER STOVE AND THE OTHER SIX BURNERS. I COULD |
| | NOT FIND THE 18 K BTU P10B SPECIFICATIONS. WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE ON DRAWING PER 2020 FBC FG SECS. 402.4.1, |
| | 402.4.2. |
| | |
| | 3. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS PER THE 2020 |
| | FBC FG SEC. 410.1. |
| | |
| | 4. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC FG SEC |
| | 410.2? |
| | |
| | 5. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS |
| | ISOMERIC PER THE 2020 FBC FG SEC. 409.5? |
| | |
| | 6. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | 7. WOULD YOU PLEASE PROVIDE A DRIP LEG BEFORE THE |
| | EQUIPMENT IS INSTALLED PER THE 2020 FBC FG 408.2. |
| | |
| | 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| | 10.4, 10.5 OF NFPA 96-08. A READILY ACCESSIBLE MEANS |
| | FOR MANUAL ACTIVATION SHALL BE LOCATED BETWEEN (42 IN. |
| | AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT |
| | OF A FIRE, SHALL BE IN A PATH OF EGRESS, AND CLEARLY |
| | IDENTIFY THE HAZARD PROTECTED. NFPA 96, SEC. 10.5.1. AT |
| | LEAST ONE MANUAL ACTUATION DEVICE SHALL BE LOCATED A |
| | MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT) |
| | FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH |
| | OF EGRESS OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO |
| | THE AHJ. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |