| Notes |
| Date |
Text |
| 2021-08-10 15:17:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE LIFE SAFETY PLAN SHEET INDICATES A TOTAL | | | OCCUPANCY LOAD OF 59, HOWEVER THE SEATING PLAN SEAT | | | INDICATES 73 SEAT ALONE. THIS WOULD NOT EVEN TAKE INTO | | | ACCOUNT OR INCLUDE, THE OTHER OCCUPIED AREAS. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 2) THE LIFE SAFETY SHEET INDICATES THE PARTY ROOM AT 96 | | | SQ FT WITH AN OCCUPANCY LOAD OF 6.4 OR 7. THE PARTY | | | ROOM SEATING PLAN INDICATES 12 SEATS. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 3) THERE REAR EXIT SIGN IS TOO DEEP WITHIN THE REAR | | | EXIT CORRIDOR TO BE SEEN FROM THE FRONT COMMON AREA. | | | | | | ADD EXIT SIGN AT REAR CORRIDOR OPEN AREA LEADING TO | | | REAR EXIT CORRIDOR. | | | | | | | | | | | | 4) THERE ARE INDICATIONS OF A NEW HOOD. ALL HOOD AND | | | HOOD SUPPRESSION SHALL BE INSTALLED UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | ADD EXIT SIGN AT REAR CORRIDOR OPEN AREA LEADING TO | | | REAR EXIT CORRIDOR | | | | | | | | | | | | | | | | | | | | | FIRE PROVISO: | | | ADD EXIT SIGN |
|