Plan Review Notes
Plan Review Notes For Permit 21080306
Permit Number 21080306
Review Stop B
Sequence Number 3
Notes
Date Text
2022-06-17 15:58:06RE-ROOF THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080306
  
 ORIGINAL COMMENT:
 1- FLORIDA PRODUCT APPROVAL SUBMITTED FL16730-R35 ALSO
 REQUIRES WITHDRAWAL RESISTANCE TESTING IN COMPLIANCE
 WITH TESTING APPLICATION STANDARD TAS 105. SEE
 LIMITATION 5.6.1. PROVIDE SIGNED AND SEALED TEST
 REPORT.
  
 RESPONSE:
 PDF THAT WAS UPLOADED TO PROJECTDOX ON 6/14/2022 UNDER
 TAS 105 FASTENER WITHDRAWAL RESISTANCE FILE IS THE
 MOISTURE SURVEY NOT THE FASTENER WITHDRAWAL RESISTANCE
 TEST. (MOISTURE SURVEY WAS SUBMITTED TWICE). REVISE AS
 REQUIRED. SUBMIT THE WITHDRAWAL RESISTANCE TESTING
 RESULTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]