2021-10-22 18:24:4210/22/21 PLANS THAT THE CONTRACTOR SIGNED WERE UPLOADED
 TO THE SIGNATURE FOLDER. THIS IS ONLY FOR DIGITALLY
 SIGNED PLANS PREPARED BY A DESIGN PROFESSIONAL,
 ARCHITECT OR ENGINEER.
  
 UPLOAD PDFS TO THE DRAWINGS FOLDER. EACH PAGE SHOULD BE
 SIGNED BY THE CONTRACTOR. SEE JAKE'S PREVIOUS COMMENT,
 CONTRACTOR CANNOT SIGN A PLAN THAT WAS PREPARED BY A
 DESIGN PROFESSIONAL.
  
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) CONTRACTOR CAN NOT SIGN SOMEONE ELSES PLANS.
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 LAND DESIGN TITLA BLOCK ON PAGE WOULD BE THE PERSON OF
 RECORD.
  
 IF THIS IS 480VOLT WORK IT IS TO BE SIGNED BY AN
 ENGINEER. 471.003(H2A)
  