| Plan Review Notes For Permit 21080247 |
| Permit Number |
21080247 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-10-22 18:24:42 | 10/22/21 PLANS THAT THE CONTRACTOR SIGNED WERE UPLOADED | | | TO THE SIGNATURE FOLDER. THIS IS ONLY FOR DIGITALLY | | | SIGNED PLANS PREPARED BY A DESIGN PROFESSIONAL, | | | ARCHITECT OR ENGINEER. | | | | | | UPLOAD PDFS TO THE DRAWINGS FOLDER. EACH PAGE SHOULD BE | | | SIGNED BY THE CONTRACTOR. SEE JAKE'S PREVIOUS COMMENT, | | | CONTRACTOR CANNOT SIGN A PLAN THAT WAS PREPARED BY A | | | DESIGN PROFESSIONAL. | | | | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CONTRACTOR CAN NOT SIGN SOMEONE ELSES PLANS. | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | LAND DESIGN TITLA BLOCK ON PAGE WOULD BE THE PERSON OF | | | RECORD. | | | | | | IF THIS IS 480VOLT WORK IT IS TO BE SIGNED BY AN | | | ENGINEER. 471.003(H2A) | | | |
|