| 2022-05-18 13:08:33 | 2ND REVIEW FMC |
| | PERMIT: 21080226 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE DRYER DUCT THAT WOULD MEET THE SIZE AND |
| | MATERIAL THICKNESS OF FRC M1502 |
| | |
| | 2) SEE PREVIOUS COMMENTS BELOW: |
| | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21080226 |
| | |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC |
| | 101.5.1.1.2 |
| | |
| | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC R403.7 |
| | |
| | |
| | 4) PLEASE SHOW A DETAIL FOR THE ANCHORING O THE OUTDOOR |
| | CONDENSING UNIT. FBC RES M1307.2 |
| | |
| | 5) PLEASE SHOW THE CONDENSATION PIPING AND THE |
| | TERMINATION LOCATION. FBC RES M1411.3 |
| | |
| | 6) PLEASE PROVIDE A MECHANICAL DRAWING THAT HAS THE |
| | DIGITAL SIGNATURE OF AN ENGINEER OR ARCHITECT, YOU MAY |
| | ALSO PROVIDE THE MECHANICAL DRAWING SIGNED BY THE |
| | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL |
| | THE SYSTEM FOR THIS PROJECT. F.S. 471.003(H) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |