| 2021-08-28 09:53:14 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21080226 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC |
| | 101.5.1.1.2 |
| | |
| | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC R403.7 |
| | |
| | 3) PLEASE SHOW THE RETURN AIR PATH FROM EXISTING |
| | BEDROOMS 1 & 2 BACK TO THE AHU. FBC RES M1602.3 |
| | |
| | 4) PLEASE SHOW A DETAIL FOR THE ANCHORING O THE OUTDOOR |
| | CONDENSING UNIT. FBC RES M1307.2 |
| | |
| | 5) PLEASE SHOW THE CONDENSATION PIPING AND THE |
| | TERMINATION LOCATION. FBC RES M1411.3 |
| | |
| | 6) PLEASE PROVIDE A MECHANICAL DRAWING THAT HAS THE |
| | DIGITAL SIGNATURE OF AN ENGINEER OR ARCHITECT, YOU MAY |
| | ALSO PROVIDE THE MECHANICAL DRAWING SIGNED BY THE |
| | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL |
| | THE SYSTEM FOR THIS PROJECT. F.S. 471.003(H) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |