Plan Review Notes
Plan Review Notes For Permit 21080223
Permit Number 21080223
Review Stop MEDGAS
Sequence Number 2
Notes
Date Text
2021-09-21 10:32:3621080223 1515 N FLAGLER DR # 301
  
 MED GAS COMMENTS:APPROVED
  
 PROVISO: PER NFPA 99-18, 15.1.5, AN INSPECTION OF THE
 EXISTING PIPING SYSTEMS SHALL BE MADE BY THE AUTHORITY
 HAVING JURISDICTION TO DETERMINE THAT CONTINUED USE OF
 SAID SYSTEMS DOES NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE. IF SUCH DETERMINATION IS MADE, THE EXISTING
 SYSTEMS MAY CONTINUE TO BE USED.
  
 DOCUMENTATION SHOWING COMPLIANCE WITH NFPA 99-18
 CHAPTER 15 AS NOTED ON PLAN SHEET P2-1; GENERAL NOTES
 2, 4 AND 5 SHALL BE ON THE JOB SITE PRIOR TO
 INSPECTION.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  