Plan Review Notes For Permit 21080223
Permit Number 21080223
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2021-08-24 10:27:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080223 1515 N FLAGLER DR # 301
  
 1ST REVIEW
 MED GAS COMMENTS:DENIED
  
 PROVISO: PER NFPA 99-18, 15.1.5, AN INSPECTION OF THE
 EXISTING PIPING SYSTEMS SHALL BE MADE BY THE AUTHORITY
 HAVING JURISDICTION TO DETERMINE THAT CONTINUED USE OF
 SAID SYSTEMS DOES NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE. IF SUCH DETERMINATION IS MADE, THE EXISTING
 SYSTEMS MAY CONTINUE TO BE USED.
  
 1. PER WPB FBC 107.2.1, PROVIDE THE RISK CATEGORY AND
 ASSESSMENT AS DETERMINED BY NFPA 99-18; 4.1 THROUGH
 4.3. THE FOLLOWING COMMENTS ARE APPLICABLE TO A
 CATEGORY 2. HOWEVER, THEY ARE SUBJECT TO CHANGE BASED
 UPON INFORMATION PROVIDED IN RESPONSE.
  
 2. IT IS UNCLEAR AS TO THE PURPOSE OF THE EXISTING ZONE
 VALVE. DOES PLAN VIEW INDICATE EXISTING PIPING FROM
 ZONE VALVE TO PROCEDURE 1 WITH NEW PROPOSED PIPING TO
 BE ADDED TO THAT ZONE? PER WPB FBC 107.2.1, CLARIFY.
 PER WPB FBC 107.2.1, PROVIDE A RISER DIAGRAM FOR THE
 OXYGEN AND NITROGEN PIPING NEW AND EXISTING PIPING
 WITHIN ZONE AND DOWN FEED FROM EXISTING.
  
 3. SHOW EXISTING SOURCE ROOM(S) FOR OXYGEN AND NITROGEN
 AND EXISTING PIPING FROM SOURCE TO EXISTING ZONE VALVE.
 SHOW ANY OTHER EXISTING BRANCH PIPING AND ZONE VALVES.
 A RISER DIAGRAM FOR THIS PIPING IS NOT REQUIRED OTHER
 THAN DOWN FEED INTO EXISTING ZONE VALVE.
  
 4. PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING
 MASTER ALARM STATION.
  
 5. PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING
 OXYGEN AND NITROGEN SUPPLY ROOM(S). PER WPB FBC 104.3,
 CONFIRM THAT APPROPRIATE SIGNAGE IS ON DOOR TO ROOM.
 SEE NFPA 99-18; 15.4.2.2.8, 15.4.2.2.9.
  
 6. PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATIONS
 FOR O2 AND NO PIPING SYSTEM INCLUDING BUT NOT LIMITED
 TO PIPE, FITTINGS, JOINTS; SEE NFPA 99-18, 15.4.4.2
  
 7. PER WPB FBC 107.2.1, SHOW OR INDICATE HOW NITROUS
 OXIDE SCAVENGING IS TO BE ACCOMPLISHED. SEE NFPA 99-18,
 15.3.3.6.
  
 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR MEDICAL
 GAS EQUIPMENT AND COMPONENTS INCLUDING BUT NOT LIMITED
 TO OUTLETS, VALVES, GAUGES, CONTROLS.
  
 9. PER WPB FBC 107.2.1, INDICATE THE BUILDING SYSTEM
 CATEGORY THAT THIS FACILITY OPERATES UNDER. SEE NFPA
 99-18, 4.1 THROUGH 4.1.4.
  
 10. PER WPB FBC 107.2.1, ADD NOTE, PIPING SHALL BE
 SUPPORTED IN ACCORDANCE WITH NFPA 99-18, TABLE
 15.4.5.6.5
  
 11. PER WPB FBC 107.2.1, ADD NOTE, PROVIDE
 DOCUMENTATION OF FOR OXYGEN AND NITROUS OXIDE PIPE,
 FITTINGS, VALVES, GAS/VACUUM OUTLETS/INLETS AND OTHER
 PIPING COMPONENTS HAVE BEEN CLEANED FOR OXYGEN BY THE
 MANUFACTURER PRIOR TO INSTALLATION IN ACCORDANCE WITH
 CGA G-4.1 AS REQUIRED BY NFPA 99-18, 15.4.4.2.1. NOTE;
 FITTINGS SHALL BE PERMITTED TO BE CLEANED BY A SUPPLIER
 OR AGENCY OTHER THAN THE MANUFACTURER WITH PROPER
 DOCUMENTATION.
  
 12. PER WPB FBC 107.2.1, PROVIDE NOTE STATING PER NFPA
 99-18, 15.4.2.1.1, 15.4.2.1.2, MEDICAL GAS (OXYGEN AND
 NITROUS OXIDE) INSTALLERS SHALL BE CERTIFIED IN
 ACCORDANCE WITH ASSE 1060. INSTALLER SHALL NOT USE HIS
 CERTIFICATION TO OVERSEE INSTALLATION BY NON-CERTIFIED
 INDIVIDUALS.
  
 12. PER WPB FBC 107.2.1, PROVIDE NOTE STATING PER NFPA
 99-18, 15.4.2.1.3, 15.4.2.1.3, BRAZING OF MEDICAL GAS
 (OXYGEN AND NITROUS OXIDE) SYSTEMS SHALL BE PERFORMED
 BY INDIVIDUALS WHO ARE QUALIFIED ACCORDANCE WITH
 15.4.6.1. PRIOR TO INSTALLATION REQUIRING BRAZING, THE
 INSTALLER (CERTIFIED) SHALL PROVIDE DOCUMENTATION OF UP
 TO DATE BRAZING PROCEDURES AND INDIVIDUAL BRAZERS
 SHOWING COMPLIANCE WITH 15.4.6.1.
  
 13. PER WPB FBC 104.3, PROVIDE NOTE STATING INSTALLERS
 CERTIFICATIONS SHOWING COMPLIANCE WITH ASSE 1060 AND
 BRAZERS CERTIFICATIONS SHOWING COMPLIANCE WITH
 15.4.6.1.
  
 14. PER WPB FBC 104.3, PROVIDE NOTE STATING TIE IN OF
 NEW PIPING TO EXISTING SYSTEMS SHALL COMPLY WITH NFPA
 99-18, 15.4.7.5.7 THROUGH 15.4.7.5.7.5.
  
 15. PER WPB FBC 104.3, PROVIDE NOTE STATING PER NFPA
 99-18, 15.4.2.11, LABELING/IDENTIFICATION OF PIPING
 SYSTEMS SHALL COMFORM TO TABLE 5.1.11.
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH