| Plan Review Notes For Permit 21080195 |
| Permit Number |
21080195 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-22 13:12:46 | 8TH FLOOR ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW ALL FIRE RATED DOORS TO BE SELF CLOSING | | | AND SELF LATCHING FBC 716.5.9 | | | 2) DRAWING A4.00 SHOWS A NEW 3' OPENING TO THE STAIRS - | | | DRAWING S-1.00 A SHOWS A NEW 6' OPENING - PLEASE | | | CLARIFY - OPENINGS SHOULD MATCH. | | | 3) DRAWING S-1.00A SHOWS A CUT SECTION REFERRING TO | | | DRAWING S5.15 - DRAWING S5.15 WAS NOT ADDED TO | | | PROJECTDOX. | | | 4) PLEASE SHOW THE GLAZED DOORS IN THE 1 HOUR FIRE | | | BARRIER TO COMPLY WITH REQUIREMENTS - FIRE RATED | | | GLAZING, SELF CLOSING, SELF LATCHING ETC PER FBC 716 | | | 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS - ALL | | | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE DESIGNER OF RECORD FBC WPB 107 | | | |
|