| 2021-11-09 11:09:05 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:21080182 |
| | ADD: 4700 BROADWAY AVE. |
| | CONT: RETAIL CONTRACTORS |
| | TEL: 352-302-5496 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. NOV. 09TH/2021 |
| | ACTION: DENIED |
| | ****NO TRANSMITTAL LETTER **** WAS SUBMITTED LISTING |
| | THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION |
| | OF THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1) SEMI-COMPLIED. 1ST ROUND OF COMMENTS. THE 3 |
| | SUBMITTED PLANS FIXTURE / HARDWARE PLAN, FLOOR PLAN & |
| | MERCHANDISE PLAN WERE NOT DESIGNED BY EITHER A ENGINEER |
| | OR ARCHITECT, THE CONTRACTOR (QUALIFIER) MUST TAKE |
| | OWNERSHIP OF ALL 3 PLANS. CERTIFICATION BY CONTRACTOR. |
| | 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| | DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | |
| | 2) 2ND REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE & |
| | HARDWARE PLAN SHOWS NEW COOLERS & FREEZERS. THE PLANS |
| | ARE SILENT AS TO IF THE CONDENSERS ARE GOING TO BE |
| | REMOTE ROOF TOP CONDENSERS, IF SO SHOW COMPLIANCE WITH |
| | THE 2020 FBC-B: |
| | |
| | 2A) 2ND REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M- |
| | 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT, |
| | APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| | BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2B) 2ND REQUEST. 1ST ROUND OF COMMENTS |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. 2020 FBC-B 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31) (G) |
| | PRE-ENGINEERED A/C STANDS |
| | |
| | |
| | 2C) 2ND REQUEST. 1ST ROUND OF COMMENTS THE ROOF TOP A/C |
| | STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE DESIGNER |
| | OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS |
| | CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP |
| | COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF |
| | HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED |
| | THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT |
| | VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND |
| | TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY |
| | THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO |
| | THE BUILDING DEPARTMENT. |
| | |
| | 2D) 2ND REQUEST. 1ST ROUND OF COMMENTS LATERAL |
| | FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP EQUIPMENT, |
| | CURBS, FANS OR A/C STANDS, AND OR VENTS, DETAILED |
| | ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL AS FROM |
| | THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2020 |
| | FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 2E) 2ND REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M 306.5 |
| | EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR |
| | APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE |
| | ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO |
| | CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO |
| | ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR |
| | EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS |
| | SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER |
| | THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS |
| | HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL |
| | NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS |
| | INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL |
| | BE MEASURED TO THE TOP OF THE PARAPET WALL. |
| | |
| | 2F) 2ND REQUEST. 1ST ROUND OF COMMENTS 2020 FBC-M 306.5 |
| | EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR |
| | APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR THE |
| | ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO |
| | CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO |
| | ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR |
| | EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS |
| | SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER |
| | THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS |
| | HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL |
| | NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS |
| | INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL |
| | BE MEASURED TO THE TOP OF THE PARAPET WALL. 2017 FBC-B |
| | 1011.16 LADDERS. |
| | |
| | 3) 2ND REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE & |
| | HARDWARE PLAN SHOWS NEW CHECKOUT COUNTERS. THE CHECK |
| | OUT COUNTERS DO NOT SHOW AN ACCESSIBLE SIDE APPROACH TO |
| | ANY OF THE 3 REGISTERS, PLEASE SHOW COMPLIANCE WITH THE |
| | 2020 FBC-ACCESSIBILITY CODE SECTIONS: |
| | |
| | 3A) 2ND REQUEST. 1ST ROUND OF COMMENTS THE FIXTURE & |
| | HARDWARE FLOOR PLAN DOES NOT SHOW CLEAR FLOOR SPACE AT |
| | THE CHECK OUT COUNTER, FOE EITHER A FORWARD AND OR SIDE |
| | APPROACH SHOW COMPLIANCE WITH 305.5 POSITION. |
| | |
| | 3B) 2ND REQUEST. 1ST ROUND OF COMMENTS THERE IS NO |
| | ELEVATION VIEWS OF THE CHECKOUT COUNTERS GIVING THE |
| | HEIGHT AND COMPLIANCE WITH 904.4 SALES AND SERVICE |
| | COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL |
| | COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION |
| | OF THE COUNTERTOP SHALL EXTEND THE SAME DEPTH AS THE |
| | SALES OR SERVICE COUNTER TOP. |
| | |
| | 4) 2ND REQUEST. 1ST ROUND OF COMMENTS THE PLANS ARE |
| | SILENT ARE THE SHELVING UNITS GOING TO BE SECURED TO |
| | THE FLOOR OR MOVEABLE? 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| | WORKING FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |