2021-09-01 08:53:39WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21080182
 ADD: 4700 BROADWAY AVE.
 CONT: RETAIL CONTRACTORS
 TEL: 352-302-5496
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 01/2021
 ACTION: DENIED
 1) THE 3 SUBMITTED PLANS FIXTURE / HARDWARE PLAN, FLOOR
 PLAN & MERCHANDISE PLAN WERE NOT DESIGNED BY EITHER A
 ENGINEER OR ARCHITECT, THE CONTRACTOR (QUALIFIER) MUST
 TAKE OWNERSHIP OF ALL 3 PLANS. CERTIFICATION BY
 CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2) THE FIXTURE & HARDWARE PLAN SHOWS NEW COOLERS &
 FREEZERS. THE PLANS ARE SILENT AS TO IF THE CONDENSERS
 ARE GOING TO BE REMOTE ROOF TOP CONDENSERS, IF SO SHOW
 COMPLIANCE WITH THE 2020 FBC-B:
  
 2A) 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2B) FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS. 2020 FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31) (G)
 PRE-ENGINEERED A/C STANDS
  
  
 2C) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 2D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2E) 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
 WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE
 LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET
 WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE
 PARAPET WALL.
  
 2F) 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
 WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE
 LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET
 WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE
 PARAPET WALL. 2017 FBC-B 1011.16 LADDERS.
  
 3) THE FIXTURE & HARDWARE PLAN SHOWS NEW CHECKOUT
 COUNTERS. THE CHECK OUT COUNTERS DO NOT SHOW AN
 ACCESSIBLE SIDE APPROACH TO ANY OF THE 3 REGISTERS,
 PLEASE SHOW COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY
 CODE SECTIONS:
  
 3A) THE FIXTURE & HARDWARE FLOOR PLAN DOES NOT SHOW
 CLEAR FLOOR SPACE AT THE CHECK OUT COUNTER, FOE EITHER
 A FORWARD AND OR SIDE APPROACH SHOW COMPLIANCE WITH
 305.5 POSITION.
  
 3B) THERE IS NO ELEVATION VIEWS OF THE CHECKOUT
 COUNTERS GIVING THE HEIGHT AND COMPLIANCE WITH 904.4
 SALES AND SERVICE COUNTERS. SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 4) THE PLANS ARE SILENT ARE THE SHELVING UNITS GOING TO
 BE SECURED TO THE FLOOR OR MOVEABLE? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  