| Plan Review Notes For Permit 21080122 |
| Permit Number |
21080122 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-05-09 10:49:56 | 3RD REVIEW FMC | | | PERMIT: 21080122 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE VENTLESS HOOD MUST COMPLY WITH FMC 507.1 | | | EXCEPTION 2. PROVIDE DOCUMENTATION THAT THIS VENTLESS | | | HOOD IS LISTED AND LABELED IN ACCORDANCE WITH UL 710B. | | | | | | 2) THE COOKING APPLIANCE MUST MEET THE REQUIREMENTS OF | | | FMC 917.1. PROVIDE DOCUMENTATION THAT THIS COMMERCIAL | | | ELECTRIC COOKING APPLIANCE IS LISTED AND LABELED IN | | | ACCORDANCE WITH UL 197. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|