| 2022-09-29 13:24:40 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080122 |
| | 9/28/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS REMAINING FROM |
| | THE 1ST REVIEW ARE PRINTED BELOW WITH ADDITIONAL NOTES |
| | FOR CLARIFICATION. |
| | |
| | 2) CV-B & P-0.1: PLEASE PROVIDE ON THE PLAN A LIST OF |
| | SEPARATE PERMITS THAT ARE REQUIRED RELATING TO THE |
| | MASTER PLUMBING PERMIT- BACKFLOW PREVENTER FOR POTABLE |
| | WATER SERVICE, GREASE AND SOLIDS INTERCEPTOR |
| | INSTALLATIONS, IRRIGATION SYSTEM- SECTION 105.1 AND |
| | 107.1 WPB. |
| | |
| | DUE TO A CHANGE IN PROCESS, THE POTABLE WATER BACKFLOW |
| | PERMIT AND GREASE INTERCEPTOR PERMIT ARE REQUIRED TO BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU |
| | CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| | TO PASS. |
| | |
| | 8) P-0.1: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTION |
| | 107.2.1 WPB. |
| | |
| | NOT PROVIDED. |
| | |
| | 9) C4.0 & P1.0: THE LOCATIONS OF THE INTERCEPTORS AS |
| | SHOWN ON THE PLANS DO NOT MATCH- SECTION 107.2.1 WPB. |
| | A) PLEASE SHOW FIELD LOCATION OF SCHEDULE NOTE 4 ON |
| | C4.0. |
| | |
| | PLANS NOT CORRECTED. |
| | |
| | 10) P1.0 & P2.0: THE CLEAR WATER WASTE FROM THE HAND |
| | SINKS AND FLOOR SINKS UNDER ICE BINS AND ICE MAKERS |
| | ETC. SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND |
| | INTERCEPTOR- SECTIONS 1003.2 AND 1003.3.1 FBC P. |
| | |
| | PLANS NOT CORRECTED. THIS IS A MANDATORY REQUIRMENT IN |
| | ACCORDANCE WITH THE FBC P AND THE WPB UTILITIES DEPT- |
| | PLEASE CORRECT THE PLANS. |
| | |
| | 11) P1.0 & P2.0: THE URINAL DRAIN SHALL NOT CONNECT |
| | INTO THE MEN'S WET-VENTED HORIZONTAL BRANCH DRAIN- |
| | SECTION 912.1 FBC P. PLEASE RELOCATE THE DRAIN |
| | CONNECTION TO A POINT DOWNSTREAM OF THE WET VENTED |
| | FIXTURES. |
| | |
| | P1.1: THE URINAL DRAIN AND VENT ARE APPROVED. PROVIDE A |
| | VENT AT THE BACK-TO-BACK DOUBLE LAVATORY LOCATION TO |
| | SERVE A DRY VENT FOR THE HORIZONTAL WET VENT- SEC. |
| | 912.2.1 FBC P. |
| | |
| | 12) SHEETS P1.0 & P2.0 ARE BEING USED TO IDENTIFY BOTH |
| | THE SANITARY AND WATER PLANS. ACCORDING TO THE INDEX |
| | THE WATER PLANS SHOULD BE LABELED P1.1 AND P2.1- PLEASE |
| | CORRECT- SECTION 107.2.1 WPB. |
| | |
| | PLEASE REVIEW THE INDEX ON SHEET CV-B AND LABEL THE |
| | PLUMBING PLANS AS THEY ARE LABELED IN THE INDEX. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |