| 2022-09-26 16:22:51 | 2ND REVIEW FMC |
| | PERMIT: 21080122 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CODE CALCULATIONS PAGE 2 OF 18 HAS THE |
| | JURISDICTION AS ALACHUA COUNTY, ALACHUA, FL. 111000. |
| | PLEASE PROVIDE THE CORRECT INFORMATION AS THE |
| | JURISDICTION IS THE CITY OF WEST PALM BEACH. IT ALSO |
| | APPEARS THAT ON PAGES 5,6 AND 7 OF 18 THAT GAINESVILLE |
| | REGIONAL AP WAS USED FOR THE WEATHER INFORMATION. |
| | PROVIDE THE CORRECT LOCATION ON THIS DOCUMENT. PALM |
| | BEACH INTERNATIONAL, PBI. FBC 107.3.5 |
| | |
| | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS IS |
| | STILL USING MIAMI IAP AS THE LOCATION. THIS SHOULD SHOW |
| | WEST PALM BEACH. FBC 107.3.5 |
| | |
| | 3) PREVIOUS COMMENT: PLEASE PROVIDE SPECIFICATIONS ON: |
| | CHEFTOP OVEN, VENTLESS HOOD AND THE THERMO DRAWER. FBC |
| | 107.3.5 |
| | |
| | 4) PLEASE SHOW THE MECHANICAL EQUIPMENT ON THE ROOF |
| | WILL HAVE THE REQUIRED FALL PROTECTION. FMC 304.11 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |