| 2022-10-03 14:34:09 | NEW BUILDING - CONVENIENCE STORE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE THE PRODUCT APPROVALS FOR THE DOORS, |
| | AND ROOFING SYSTEMS THAT ARE LISTED ON PAGE CV-B - OR |
| | HAVE THE PROVIDED PRODUCT APPROVALS REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB |
| | 107.3.4 |
| | |
| | 2) DRAWINGS S1.1 SHOWS THE WIND SPEED USED FOR WIND |
| | DESIGN AS 168MPH - RISK CATEGORY II WIND SPEED SHOULD |
| | BE 170MPH PER FBC WPB SECTION 120. |
| | |
| | 3) DRAWING CV-B SHOWS ASCE 7-10 USED FOR WIND DESIGN - |
| | SHOULD BE ASCE 7-16 FBC CHAPTER 35 |
| | |
| | 4) DRAWING S1.1 SHOWS THE WIND DESIGN USING "EXPOSURE |
| | B" - THE BUILDING IS NEXT TO A LARGE LAKE - "EXPOSURE |
| | D" SHOULD BE USED. |
| | |
| | 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - |
| | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE |
| | ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON |
| | THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL |
| | SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT |
| | OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A |
| | HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT |
| | APPROVAL - SEE GENERAL NOTES IN THE PRODUCT APPROVAL. |
| | |
| | 6) THE SOIL REPORT PROVIDED - DOES NOT SHOW AS |
| | DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| | DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |
| | |
| | |
| | |