| 2021-09-23 08:10:55 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21080122 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CALCULATIONS MUST BE FILLED OUT |
| | COMPLETELY AND MUST SHOW THE CORRECT CITY, STATE AND |
| | JURISDICTION. FBC 107.2.1 |
| | |
| | 2) THE MECHANICAL LOAD CALCULATIONS MUST SHOW THE |
| | LOCATION OF THE PROJECT AND THE NAME OF THE PROJECT AND |
| | SHOW THE CORRECT LOCATION (WEST PALM BEACH). FBC |
| | 107.2.1 |
| | |
| | 3) PAGE 3 OF 7 OF THE MECHANICAL LOAD CALCULATIONS SHOW |
| | THE VENTILATION SIZING SUMMARY FOR RTU-1A,B. PLEASE |
| | PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1 FOR EACH USE OF SPACE. |
| | NOTE: YOU CAN USE FOOTNOTE A FOR NET FLOOR AREA. |
| | |
| | 4) PLEASE ADD A NOTE STATING THAT THE REFRIGERATION |
| | SYSTEMS WILL REQUIRE A SEPARATE PERMIT APPLICATION, |
| | SUBMITTAL AND REVIEW AS IT WILL NOT BE REVIEWED UNDER |
| | THIS PERMIT. |
| | |
| | 5) PLEASE PROVIDE SPECIFICATIONS ON: CHEFTOP OVEN, |
| | VENTLESS HOOD AND THE THERMO DRAWER. FBC 107.2.1 |
| | |
| | 6) SHEET M-0.0: THE ASHRAE STANDARD REFERENCED IN THE |
| | OUTDOOR AIR CALCULATION IS OUT OF DATE. THE 2020 FBC M |
| | REFERENCES ASHRAE 62.1-2016 PLEASE USE THIS VERSION. |
| | |
| | 7) SHEET M-0.0 IS REFERENCING MIAMI FLORIDA IN THE HVAC |
| | DESIGN PARAMETERS, PLEASE USE WEST PALM BEACH. |
| | |
| | 8) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| | FUEL SYSTEM WILL REQUIRE A SEPARATE PERMIT APPLICATION, |
| | SUBMITTAL AND REVIEW. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |