| Plan Review Notes For Permit 21080119 |
| Permit Number |
21080119 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-11-01 08:10:38 | PLEASE RESPOND TO NOTE 2 FROM PREVIOUS REVIEW BELOW: | | | | | | 2) THE RESPONSE LETTER DATED AUG. 30, 2021 STATES THAT | | | THE OUTDOOR AIR FOR THE LOBBY AND CORRIDOR 2 IS BEING | | | SUPPLIED BY NATURAL VENTILATION. AS I LOOK AT THE | | | SUBMITTED DRAWING I SEE DOORS ENCLOSING THESE AREAS. | | | PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW THESE AREAS | | | ARE TO BE NATURALLY VENTILATED. PLEASE REMEMBER IF | | | THERE ARE DOORS IN THE OPENINGS YOU CAN NOT USE THE | | | NATURAL VENTILATION METHOD OF FBC M 402. PLEASE ALSO | | | REMEMBER THAT ADJOINING SPACES WOULD BE REQUIRED TO | | | MEET THE 8 PERCENT OF THE FLOOR AREA IN FBC M 402.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|