2021-11-01 08:10:38PLEASE RESPOND TO NOTE 2 FROM PREVIOUS REVIEW BELOW:
  
 2) THE RESPONSE LETTER DATED AUG. 30, 2021 STATES THAT
 THE OUTDOOR AIR FOR THE LOBBY AND CORRIDOR 2 IS BEING
 SUPPLIED BY NATURAL VENTILATION. AS I LOOK AT THE
 SUBMITTED DRAWING I SEE DOORS ENCLOSING THESE AREAS.
 PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW THESE AREAS
 ARE TO BE NATURALLY VENTILATED. PLEASE REMEMBER IF
 THERE ARE DOORS IN THE OPENINGS YOU CAN NOT USE THE
 NATURAL VENTILATION METHOD OF FBC M 402. PLEASE ALSO
 REMEMBER THAT ADJOINING SPACES WOULD BE REQUIRED TO
 MEET THE 8 PERCENT OF THE FLOOR AREA IN FBC M 402.3
  
 MICHAEL EDWARDS