| 2021-09-30 08:42:30 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21080119 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND THE |
| | ENERGY CALCULATIONS ARE NOT IN THE UPLOADED FILES FOR |
| | THIS PROJECT. PLEASE SUBMIT THEM SO I CAN REVIEW THE |
| | DOCUMENTS. FBC 107.2.1 |
| | |
| | 2) THE RESPONSE LETTER DATED AUG. 30, 2021 STATES THAT |
| | THE OUTDOOR AIR FOR THE LOBBY AND CORRIDOR 2 IS BEING |
| | SUPPLIED BY NATURAL VENTILATION. AS I LOOK AT THE |
| | SUBMITTED DRAWING I SEE DOORS ENCLOSING THESE AREAS. |
| | PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW THESE AREAS |
| | ARE TO BE NATURALLY VENTILATED. PLEASE REMEMBER IF |
| | THERE ARE DOORS IN THE OPENINGS YOU CAN NOT USE THE |
| | NATURAL VENTILATION METHOD OF FBC M 402. PLEASE ALSO |
| | REMEMBER THAT ADJOINING SPACES WOULD BE REQUIRED TO |
| | MEET THE 8 PERCENT OF THE FLOOR AREA IN FBC M 402.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |