Plan Review Notes
Plan Review Notes For Permit 21080119
Permit Number 21080119
Review Stop M
Sequence Number 2
Notes
Date Text
2021-09-30 08:42:302ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21080119
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND THE
 ENERGY CALCULATIONS ARE NOT IN THE UPLOADED FILES FOR
 THIS PROJECT. PLEASE SUBMIT THEM SO I CAN REVIEW THE
 DOCUMENTS. FBC 107.2.1
  
 2) THE RESPONSE LETTER DATED AUG. 30, 2021 STATES THAT
 THE OUTDOOR AIR FOR THE LOBBY AND CORRIDOR 2 IS BEING
 SUPPLIED BY NATURAL VENTILATION. AS I LOOK AT THE
 SUBMITTED DRAWING I SEE DOORS ENCLOSING THESE AREAS.
 PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW THESE AREAS
 ARE TO BE NATURALLY VENTILATED. PLEASE REMEMBER IF
 THERE ARE DOORS IN THE OPENINGS YOU CAN NOT USE THE
 NATURAL VENTILATION METHOD OF FBC M 402. PLEASE ALSO
 REMEMBER THAT ADJOINING SPACES WOULD BE REQUIRED TO
 MEET THE 8 PERCENT OF THE FLOOR AREA IN FBC M 402.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  