Plan Review Notes
Plan Review Notes For Permit 21080114
Permit Number 21080114
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-08-11 13:54:28****CONTACTED BY APPLICANT, REQUIRED INFO PROVIDED,
 PASS 8/25/21.PML*****
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS ON THE SITE PLAN THAT THE
 PROPOSED AWNING STRUCTURES ARE OVER EXITS.
  
 THERE ARE NO INDICATIONS THAT THE FABRIC MATERIAL HAS
 FIRE RETARDENT CERTIFICATIONS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved