| 2021-10-08 10:42:44 | RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080079 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED: |
| | BASED ON THE AERIAL VIEWS ON THE PROPERTY APPRAISER |
| | WEBSITE, IT LOOKS LIKE SOME OPENINGS ARE IN THE END |
| | ZONE NOT IN THE INTERIOR ZONE AND THE BUILDING |
| | DIMENSIONS ARE WRONG. THIS IS CRITICAL BECAUSE PRODUCT |
| | APPROVALS SUBMITTED MAY NOT MEET THE DESIGN PRESSURES. |
| | REVISE CALCULATIONS SUBMITTED SHOWING THE OPENINGS THAT |
| | ARE LOCATED IN THE END ZONE OR PROVIDE SITE SPECIFIC |
| | DESIGN WIND PRESSURES SHOWING THE ACTUAL BUILDING |
| | DIMENSIONS AND WALL ZONES. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | |
| | 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE |
| | THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK |
| | PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN |
| | PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED: |
| | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | REPEAT COMMENT. |
| | |
| | |
| | NOTE: SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. WINDOW |
| | OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE |
| | REQUIRED WHEN THE FOLLOWING APPLY: |
| | IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS |
| | AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES |
| | REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| | WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM |
| | F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS |
| | REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE |
| | REPLACEMENT WINDOW: |
| | 1.THE WINDOW IS OPERABLE; |
| | 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE |
| | SASH AND THE FRAME; |
| | 3.ONE OF THE FOLLOWING APPLIES: |
| | 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING |
| | UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT |
| | A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE |
| | FINISHED FLOOR; OR |
| | 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES |
| | REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| | THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS |
| | THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR; |
| | 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW |
| | PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE |
| | WINDOW IS IN ITS LARGEST OPENED POSITION; AND |
| | 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE |
| | WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE |
| | BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN |
| | 72 INCHES (1829 MM). |
| | THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO |
| | RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY |
| | OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING |
| | AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED |
| | BY THE FLORIDA BUILDING CODE, BUILDING |
| | |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |