| 2021-09-03 14:55:18 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080079 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED: |
| | A)BUILDING MEAN ROOF HEIGHT OF 82' IS INCORRECT. THIS |
| | IS A 10 STORY BUILDING. SEE BUILDING AND REVISE ALL THE |
| | DESIGN CRITERIA AS REQUIRED, INCLUDING THE VELOCITY |
| | PRESSURE COEFFICIENT. |
| | CHAPTER 30 ASCE 7-16. |
| | |
| | B) BUILDING DIMENSION OF 60' IS INCORRECT. SEE BUILDING |
| | AND REVISE THE DESIGN CRITERIA AS REQUIRED, INCLUDING |
| | THE END ZONE DISTANCE. |
| | CHAPTER 30 ASCE 7-16. |
| | |
| | C) BASED ON THE END ZONE DISTANCE, IT LOOKS LIKE SOME |
| | WINDOWS, DOORS MAY BE IN THE END ZONE NOT THE INTERIOR |
| | ZONE. SEE BUILDING AND REVISE CALCULATIONS AS REQUIRED. |
| | CHAPTER 30 ASCE 7-16 |
| | |
| | D)ENGINEER TO CLARIFY WHY THE DEVICE CALCULATIONS HAVE |
| | AN ELEVATION OF 7 FEET?. THIS IS A 10 STORY BUILDING. |
| | CHAPTER 30 ASCE 7-16 |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | E) WIND PRESSURE CALCULATIONS HAVE A COPY OF THE |
| | ENGINEER'S SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE |
| | AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE |
| | OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL |
| | AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL |
| | FOR RECORDS RETENTION. |
| | |
| | 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE |
| | THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK |
| | PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN |
| | PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED: |
| | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |