| 2021-08-10 10:14:53 | 08/10/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT |
| | SYSTEM. A COMPLETE EVALUATION OF ALL GAS SYSTEMS AND |
| | EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO |
| | CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT |
| | THE OWNER'S EXPENSE. PLEASE INCLUDE THE CURRENT AND NEW |
| | GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE |
| | OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. METAL PIPES INSTALLED OUTDOORS SHALL BE ELEVATED NOT |
| | LESS THAN 3 1/2 INCHES ABOVE THE GROUND AND WERE |
| | INSTALLED ACROSS ROOF SURFACES PER THE 2020 FBC SEC |
| | G2415.9 (404.9) ABOVE-GROUND PIPING. |
| | |
| | 3. GAS RISER DIAGRAM REQUIRED AND ON ISOMETRIC DRAWING |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2, AND WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| | GAS. |
| | |
| | 4. WHEN USING THE LONGEST LENGTH OF PIPING FROM THE |
| | POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE |
| | LOAD ON THE SECTION. SHOW THE DISTANCE FROM THE POINT |
| | OF DELIVERY (GAS METER) TO THE MOST REMOTE OUTLET IN |
| | THE BUILDING AND/OR SYSTEM PER THE 2020 FBC RES. SECS. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 5. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. TELL US IF (LP OR NATURAL) PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 8. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. |
| | |
| | 9. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE |
| | PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| | |
| | 10. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 11. PLEASE SUBMIT THE SIZING TABLE USED IN THE DESIGN |
| | FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF |
| | PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER |
| | THE 2020 FBC RES. SEC. G2413.3. |
| | |
| | 12. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE |
| | ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5. |
| | |
| | 13. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | 14. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| | APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 15. IF APPLICABLE, PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 16. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION. WOULD YOU PLEASE PROVIDE A BONA FIDE |
| | SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 109.3 BUILDING PERMIT VALUATIONS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |