| 2021-09-14 09:53:55 | 09/14/21 2ND POOL PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM |
| | SYSTEM FLOW COMPONENTS IS MISSING THE HEAT PUMP. THE |
| | TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM |
| | COMPONENTS, INCLUDING SUCTION AND RETURN PIPING, |
| | FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL |
| | SYSTEM COMPONENTS EXCEPT THE PUMP PER THE ANSI/APSP/ICC |
| | 7 - 2015 SECS. 4.4.9, 4.4.9.1 MAXIMUM SYSTEM FLOW |
| | RATE?UNSECURED CONTROL SYSTEMS. |
| | |
| | 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 3. ALL POOL HEATERS SHALL BE EQUIPPED WITH A READILY |
| | ACCESSIBLE ON-OFF SWITCH THAT IS MOUNTED OUTSIDE THE |
| | HEATER TO ALLOW SHUTTING OFF THE HEATER WITHOUT |
| | ADJUSTING THE THERMOSTAT SETTING PER THE 2020 |
| | FBC-ENERGY ? SEC. R403.10.1 |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |