| 2021-08-23 07:48:09 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC 107 BASED ON THE DOCUMENTS SUBMITTED IT APPEARS |
| | THAT THE SCOPE OF WORK INCLUDES TWO STRUCTURES, FLAT |
| | AND SHINGLE ROOFS. PROVIDE A PERMIT APPLICATION WITH AN |
| | ACCURATE DESCRIPTION. INCLUDE SQUARE FOOT AREA OF EACH |
| | ROOF TYPE FOR EACH STRUCTURE, EITHER ON THE APPLICATION |
| | OR ON THE ROOF PLAN. |
| | |
| | 2. SEE PREVIOUS LIST. A "DESIGN PRESSURE QUESTIONNAIRE" |
| | WAS UPLOADED, THAT FORM IS FOR YOU TO GIVE TO YOUR |
| | ENGINEER (FLORIDA ENGINEERING & TESTING) FOR THEM TO |
| | PROVIDE YOU WITH ENHANCED FASTENING CALCULATIONS. IT IS |
| | NOT CLEAR WHY THIS WAS PROVIDED (IT HAS BEEN LOCKED SO |
| | THAT DOCUMENT WILL NOT BE ISSUED). NO OTHER NEW |
| | DOCUMENTS WERE SUBMITTED. |
| | |
| | 3. THE PALM BEACH COUNTY ROOFING FORM PROPOSES DESIGN |
| | PRESSURES OF -79.8 FOR ZONES 2 AND 3. USE OF ZONE 2 |
| | PRESSURES FOR ZONE 3 REQUIRES A PARAPET BUT NONE IS |
| | SHOWN ON THE ROOF PLAN. CLARIFY. |
| | |
| | 4. PAGE 14 OF 42 FOR NOA 17-1003.04 WAS MARKED AS THE |
| | PROPOSED ASSEMBLY. IT HAS A DESIGN PRESSURE LIMINTATION |
| | OF -60PSF. SEE PAGE 42 OF THE NOA, GENERAL LIMITATION |
| | #7. CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL ARE |
| | REQUIRED, FBC R 301. |
| | |
| | |