| 2021-09-01 15:41:51 | RESIDENTIAL (R3) ALTERATION LEVEL 3, BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21071631 |
| | |
| | NOTE: |
| | LEVEL 3 ALTERATION. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE AS REQUIRED |
| | BY SEC. 604 FBC-EXISTING BUILDING, SEC. 901.2 |
| | FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING |
| | BUILDING. |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER |
| | OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT. |
| | |
| | |
| | 1-ENERGY CALCULATIONS SUBMITTED: |
| | A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION. |
| | |
| | B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. PROVIDE CORRECT OWNER'S NAME. THE PERMIT OFFICE |
| | IS CITY OF WEST PALM BEACH NOT PALM BEACH COUNTY. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | C)REVISE ITEM #1 ON PAGE 1. THIS IS NOT NEW |
| | CONSTRUCTION. |
| | SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | D)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION |
| | ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?. |
| | "DETACHED" IS NOT THE ANSWER. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)WALL INSULATION ON ITEM #10 ON PAGE 1 DOESN'T MATCH |
| | WALL INSULATION SPECIFIED ON SHEET A-2. SEE PLANS AND |
| | REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F)CLEARLY PROVIDE THE NAME OF PERSON PERFORMING THE |
| | ANALYSIS AND GENERATING THE REPORT AS REQUIRED BY SEC. |
| | R405.4.2.1 FBC- ENERGY CONSERVATION. |
| | |
| | G)PROVIDE CORRECT INFORMATION IN THE SPACES SECTION ON |
| | PAGE 2. IS MISSING THE NUMBER OF OCCUPANTS. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H) ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 3 IS |
| | MISSING THE INFORMATION FOR THE FLAT ROOF. THE ROOF OF |
| | THIS BUILDING IS PITCHED AND FLAT. SEE PLANS AND |
| | BUILDING AERIAL VIEW. REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | I)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH |
| | PLANS. SEE ELEVATIONS AND REVISE AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | J) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | 2- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE |
| | BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL. |
| | |
| | 3- PROVIDE DOOR STRUCTURAL BUCK DETAIL SHOWING |
| | COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL. |
| | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| | THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- SHEET A-3: THERE ARE SEVERAL NOTES REFERENCING THE |
| | 2014 RESIDENTIAL CODE. THE CURRENT CODE IS |
| | FBC-RESIDENTIAL SEVENTH EDITION (2020). REVISE ALL |
| | NOTES REFERENCING THE OLD CODE. |
| | CHAPTER 553.73 F.S. |
| | |
| | 5- PROVIDE ICC EVALUATION REPORT FOR THE SPRAYED FOAM |
| | R-20 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 |
| | FBC-RESIDENTIAL. |
| | NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE |
| | REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 6-WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| | FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| | OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| | FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| | CLEARLY SPECIFY IF THERE IS ANY WINDOW WITH THE SILL |
| | BELOW 24". |
| | NOTE: IF REQUIRED, THEN WINDOW OPENING CONTROL DEVICE |
| | NEEDS TO COMPLY WITH ASTM F2090. PROVIDE INFORMATION |
| | FOR DEVICE TO BE INSTALLED. |
| | |
| | 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)INSWING ENTRY DOOR. |
| | B)EXTERIOR FRENCH DOORS WITH SIDELITES AS SHOWN ON |
| | PLANS. |
| | C)WINDOWS INCLUDING THOSE WITH ARCHED TOP. |
| | D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | 13-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |