2021-10-18 14:27:172ND REVIEW FBC-2020 RES.
 PERMIT- 21071627
 10/18/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-3 & G-1: THE NEW RISER SHOWS THE GAS FROM
 THE MAIN HOUSE SUPPLYING THE GAS GRILL AT THE GUEST
 HOUSE. THE CONTRACTOR AND OWNER ARE ADVISED TO CONSULT
 WITH FPU FOR INFORMATION ABOUT GAS METERING AS A
 SEPARATE METER MAY BE REQUIRED. FPU CUSTOMER SERVICE
 NUMBER IS 1-800-427-7712.
  
 2) G-1 GAS RISER:
 A) PROVIDE THE TOTAL LENGTH OF THE PIPING, AND THE
 INDIVIDUAL BRANCH AND CUT PIPE LENGTHS- SECTION
 G2413.4.1.
 B) PROVIDE THE PIPE SIZING TABLES IN ACCORDANCE WITH
 SECTION G2413.4.
  
 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE GAS GRILL- SECTION G2408.1 & G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  