| Plan Review Notes For Permit 21071627 |
| Permit Number |
21071627 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-10-18 14:27:17 | 2ND REVIEW FBC-2020 RES. | | | PERMIT- 21071627 | | | 10/18/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-3 & G-1: THE NEW RISER SHOWS THE GAS FROM | | | THE MAIN HOUSE SUPPLYING THE GAS GRILL AT THE GUEST | | | HOUSE. THE CONTRACTOR AND OWNER ARE ADVISED TO CONSULT | | | WITH FPU FOR INFORMATION ABOUT GAS METERING AS A | | | SEPARATE METER MAY BE REQUIRED. FPU CUSTOMER SERVICE | | | NUMBER IS 1-800-427-7712. | | | | | | 2) G-1 GAS RISER: | | | A) PROVIDE THE TOTAL LENGTH OF THE PIPING, AND THE | | | INDIVIDUAL BRANCH AND CUT PIPE LENGTHS- SECTION | | | G2413.4.1. | | | B) PROVIDE THE PIPE SIZING TABLES IN ACCORDANCE WITH | | | SECTION G2413.4. | | | | | | 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT THE | | | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL | | | FOR THE GAS GRILL- SECTION G2408.1 & G2447.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|