| 2022-07-25 17:47:23 | FAILED |
| | |
| | REPEAT COMMENT: PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | *** NO WRITTEN RESPONSE PROVIDED. |
| | |
| | 1) THE PLANS SUBMITTED WITH THIS TOWER PERMIT DO NOT |
| | MATCH THE PLANS THAT WERE TO BE APPROVED AS PART OF THE |
| | LATEST MINOR PLANNED DEVELOPMENT AMENDMENT OR THE |
| | APPROVED FOUNDATION PERMIT. ALL PLANS WILL NEED TO SHOW |
| | THE LATEST CODE COMPLIANT CONDITIONS AND BE INTERNALLY |
| | CONSISTENT. DUE TO THE PLAN CHANGES, PLANNING WILL HOLD |
| | OFF ON THE FORMAL ISSUANCE OF THE MINOR PLANNED |
| | DEVELOPMENT AMENDMENT UNTIL THE VERTICAL PERMIT PLANS |
| | ARE APPROVED. AT SUCH TIME, PLANNING WILL REQUEST TWO |
| | SETS OF THE APPROVED PLANS, INCLUDING AN ELECTRONIC |
| | COPY, SO THAT THE MINOR PLANNED DEVELOPMENT AMENDMENT |
| | CAN BE ISSUED. |
| | |
| | 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. |
| | 13-19, PROVIDE VERIFICATION THAT ALL SURFACES OF THE |
| | BUILDING'S EXTERIOR FACADE, TO INCLUDE GLAZING, ARE |
| | DESIGNED OR TREATED TO MINIMIZE THE IMPACTS OF GLARE |
| | AND REFLECTION OF HIGH INTENSITY LIGHT FROM THE |
| | BUILDING'S FACADE ONTO SURROUNDING PROPERTIES. |
| | |
| | 3) REPEAT COMMENT: PROVIDE AN FAA EXTENSION LETTER FOR |
| | THE BUILDING. THE LETTER THAT STAFF HAS ON FILE EXPIRED |
| | IN JANUARY 2022. |
| | |
| | 4) REPEAT COMMENT: SHEET 00.200 REFERENCES SAUNA SQUARE |
| | FOOTAGE ON THE ROOF LEVEL. ROOFTOP SAUNAS ARE |
| | CONSIDERED AMENITIES AND ARE NOT PERMITTED TO EXCEED |
| | THE HEIGHT OF THE ROOF DECK (300 FEET). ALL SAUNA |
| | REFERENCES AND FACILITIES MUST BE REMOVED FROM THE |
| | ENTIRE PLAN SET. |
| | |
| | 5) REPEAT COMMENT: THE SURVEY PROVIDED A S-1-00 IS NOT |
| | THE LATEST SURVEY THAT WAS SUBMITTED WITH THE |
| | FOUNDATION PERMIT. THE LATEST, ACCURATE SURVEY IS |
| | REQUIRED TO BE INCLUDED WITH THE PLANS. |
| | |
| | 6) REPEAT COMMENT: THE CIVIL PLANS ARE NOT THE VERSION |
| | THAT WAS SUBMITTED WITH THE APPROVED FOUNDATION PERMIT. |
| | ALL PERMITS NEED TO INCLUDE THE SAME LATEST, ACCURATE |
| | PLANS. |
| | |
| | 7) UPDATED COMMENT: THE PLANS SUBMITTED AS PART OF THE |
| | MINOR PLANNED DEVELOPMENT AMENDMENT SHOW THE WEST |
| | SETBACK DIMENSION OF 5 FEET 6 INCHES FOR THE GENERATOR |
| | PIT, WHICH WAS ALSO REFLECTED ON THE APPROVED |
| | FOUNDATION PERMIT. THE SHEET 1.100 PROVIDED RECENTLY TO |
| | PLANNING STAFF SHOWS A SETBACK OF 5 FEET 7 INCHES. THIS |
| | PERMIT SHOWS A WEST SETBACK OF 5 FEET 3 INCHES (OCCURS |
| | ON SHEETS A1.100 AND A1.1B1). THE PERMITS AND MINOR |
| | PLANNED DEVELOPMENT AMENDMENT NEED TO INCLUDE THE SAME |
| | LATEST, ACCURATE PLANS. NOTE: THE PLAN ORIGINALLY |
| | APPROVED BY THE CITY COMMISSION SHOWED A SETBACK FOR |
| | THE GENERATOR PIT OF 5 FEET EVEN. |
| | |
| | 8) REPEAT COMMENT: SHEET A1.1B1 DOES NOT MATCH THE |
| | APPROVED FOUNDATION PERMIT RESUBMITTAL. ALL PERMITS |
| | NEED TO INCLUDE THE SAME LATEST, ACCURATE PLANS. *** |
| | THE SETBACK DISCREPANCY FROM COMMENT #7 IS ONE EXAMPLE. |
| | |
| | 9) REPEAT COMMENT: PLEASE EXPLAIN HOW THE BUILDING |
| | INCREASED FROM A NORTH/SOUTH DIMENSION OF 137 FEET 5 |
| | INCHES ON THE FOUNDATION PLAN TO 137 FEET 9 INCHES ON |
| | THE TOWER PLAN WITHOUT IMPACTING THE SIDE SETBACKS? |
| | NOTE THE MINIMUM SETBACKS MUST BE MAINTAINED. SHOWN ON |
| | SHEET A1.1B1. |
| | |
| | 10) UPDATED COMMENT: THE ORIGINALLY APPROVED PLANS |
| | SHOWED THE FIRST FLOOR OF THE BUILDING WITH A FLAT |
| | EASTERN FACADE. THE MINOR PLANNED DEVELOPMENT AMENDMENT |
| | SUBMITTAL AND APPROVED FOUNDATION PERMIT LIFE SAFETY |
| | PLAN SHOW A CURVED EASTERN FACADE. SOME OF THE PLANS |
| | SUBMITTED WITH THIS PERMIT SHOW THE FLAT EASTERN FACADE |
| | AGAIN, WHILE OTHERS (EX. PLUMBING). PLEASE CLARIFY |
| | WHICH VERSION IS CORRECT. ALL PERMITS NEED TO INCLUDE |
| | THE SAME LATEST, ACCURATE PLANS. IF THE PLAN IS FOR A |
| | FLAT FACADE, THEN THE FOUNDATION PERMIT SET NEEDS TO BE |
| | REVISED. |
| | |
| | 11) REPEAT COMMENT: THE DIMENSION LINES LISTED TO THE |
| | COLUMNS DO NOT ACTUALLY REACH THE COLUMNS. |
| | |
| | 12) REPEAT COMMENT: PROVIDE THE SETBACKS FROM THE FACE |
| | OF GLASS TO THE PROPERTY LINE FOR EACH FLOOR PLAN. THIS |
| | WAS SHOWN ON THE MINOR PLANNED DEVELOPMENT AMENDMENT |
| | PLAN. |
| | |
| | 13) REPEAT COMMENT: THE ELEVATION DRAWINGS DO NOT MATCH |
| | THE ONES SUBMITTED AS PART OF THE MINOR PLANNED |
| | DEVELOPMENT AMENDMENT. ALL SUBMITTALS NEED TO INCLUDE |
| | THE SAME LATEST, ACCURATE PLANS. |
| | |
| | 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE |
| | PERMITS WITH PLANS: |
| | |
| | A. THE WALLS, FENCES, GATES AND COLUMNS |
| | B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| | PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| | C. LANDSCAPE |
| | D. IRRIGATION |
| | E. GENERATOR |
| | F. WATER FEATURES |
| | G. PARKING STRIPING |
| | H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| | ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| | PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| | OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| | REQUIRED WITH THE PERMITS. |