| Date |
Text |
| 2022-06-01 17:15:04 | 1) IF THE ENGINEER OF RECORD WOULD LIKE TO USE THE |
| | EXCEPTION TO FMC 403.3.1.1 THEY WOULD NEED TO SUBMIT |
| | THE STATISTICAL DATA TO THE BUILDING OFFICIAL TO |
| | APPROVE OR DENY. |
| | |
| | 2) THE TREATMENT ROOM, BARBER AREA WILL NEED 61 CFM?S |
| | OF EXHAUST. FMC TABLE 403.3.1.1 |
| | |
| | 3) THE DRESSING ROOMS WILL REQUIRE EXHAUST AIR. THE 477 |
| | SQ FT WILL NEED 119 CFM?S AND THE 328 SQ. FT. WILL NEED |
| | 82 CFM?S FMC TABLE 403.3.1.1 |
| | |
| | 4) THE CHANGING ROOMS ON SHEET M2.103D WILL NEED |
| | EXHAUST. THE 30 SF CHANGING ROOM WILL REQUIRE 8 CFM?S |
| | EXHAUST AND THE 27SF CHANGING ROOM WILL REQUIRE 7 CFM?S |
| | EXHAUST. FMC TABLE 403.3.1.1 |
| | |
| | 5) WHY IS THE DINING ROOM BEING CLASSIFIED AS A |
| | LOBBY/PREFUNCTION? THE DINING ROOM WILL REQUIRE 723 |
| | CFM?S OF OUTDOOR AIR. |
| | |
| | 6) THE WARMING KITCHEN/BREAKROOM WILL REQUIRE OUTDOOR |
| | AIR AND EXHAUST. |
| | |
| | 7) SHEET M2.101D: THE OFFICE AND MAILROOM WILL REQUIRE |
| | OUTDOOR AIR BUT THE FCU-2 SUPPLYING THIS AREA DOES NOT |
| | SHOW AN OUTDOOR AIR DUCT AT THE RETURN. |
| | |
| | 8) THE MEN?S AND WOMEN?S SPAS WILL REQUIRE OUTDOOR AIR. |
| | FMC 403.3.1.1 |
| | VENTILATION RATES FOR OCCUPANCIES NOT REPRESENTED IN |
| | TABLE 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY |
| | CLASSIFICATION THAT IS MOST SIMILAR IN TERMS OF |
| | OCCUPANT DENSITY, ACTIVITIES AND BUILDING |
| | CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED |
| | ENGINEERING ANALYSIS. |
| | |