| 2022-05-17 15:24:36 | FAILED |
| | |
| | REPEAT COMMENT: PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | |
| | 1) THE PLANS SUBMITTED WITH THIS TOWER PERMIT DO NOT |
| | MATCH THE PLANS THAT HAVE BEEN APPROVED AS PART OF THE |
| | LATEST MINOR PLANNED DEVELOPMENT AMENDMENT OR THE |
| | APPROVED FOUNDATION PERMIT. THE REPEAT COMMENTS WILL |
| | CONTINUE TO BE ISSUED UNTIL THE PLANS ALIGN AND MEET |
| | ZONING REQUIREMENTS. |
| | |
| | 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. |
| | 13-19, PROVIDE VERIFICATION THAT ALL SURFACES OF THE |
| | BUILDING'S EXTERIOR FACADE, TO INCLUDE GLAZING, ARE |
| | DESIGNED OR TREATED TO MINIMIZE THE IMPACTS OF GLARE |
| | AND REFLECTION OF HIGH INTENSITY LIGHT FROM THE |
| | BUILDING'S FACADE ONTO SURROUNDING PROPERTIES. |
| | |
| | 3) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. |
| | 13-19, PROVIDE VERIFICATION THAT THE DEVELOPER HAS |
| | CONTRACTED WITH AN INDEPENDENT PROFESSIONAL THAT IS |
| | ACCREDITED IN THE SPECIFIC CERTIFICATION BEING UTILIZED |
| | TO MEET THIS DEVELOPMENT REGULATION TO ACT AS A GREEN |
| | DEVELOPMENT REVIEW AGENT TO ENSURE THAT THE BUILDING |
| | WILL BE CONSTRUCTED IN ACCORDANCE WITH A CERTIFICATION |
| | PLAN THAT ACHIEVES TO A MINIMUM LEED SILVER LEVEL, OR |
| | EQUIVALENT GREEN BUILDING STANDARD. |
| | |
| | 4) REPEAT COMMENT: PROVIDE AN FAA EXTENSION LETTER FOR |
| | THE BUILDING. THE LETTER THAT STAFF HAS ON FILE EXPIRED |
| | IN JANUARY 2022. |
| | |
| | 5) REPEAT COMMENT: SHEET 00.200 REFERENCES SAUNA SQUARE |
| | FOOTAGE ON THE ROOF LEVEL. ROOFTOP SAUNAS ARE |
| | CONSIDERED AMENITIES AND ARE NOT PERMITTED TO EXCEED |
| | THE HEIGHT OF THE ROOF DECK (300 FEET). ALL SAUNA |
| | REFERENCES AND FACILITIES MUST BE REMOVED FROM THE |
| | ENTIRE PLAN SET. |
| | |
| | 6) REPEAT COMMENT: THE SURVEY PROVIDED A S-1-00 IS NOT |
| | THE LATEST SURVEY THAT WAS SUBMITTED WITH THE |
| | FOUNDATION PERMIT. THE LATEST, ACCURATE SURVEY IS |
| | REQUIRED TO BE INCLUDED WITH THE PLANS. |
| | |
| | 7) REPEAT COMMENT: THE CIVIL PLANS ARE NOT THE LATEST |
| | VERSION THAT WAS SUBMITTED WITH THE RECENT FOUNDATION |
| | PERMIT RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE |
| | SAME LATEST, ACCURATE PLANS. |
| | |
| | 8) REPEAT COMMENT: THE PLANS APPROVED AS PART OF THE |
| | MINOR PLANNED DEVELOPMENT AMENDMENT SHOW THE WEST |
| | SETBACK DIMENSION OF 5 FEET 6 INCHES FOR THE GENERATOR |
| | PIT, WHICH WAS ALSO REFLECTED ON THE APPROVED |
| | FOUNDATION PERMIT. THIS PERMIT SHOWS A 5 FOOT 3 INCH |
| | WEST SETBACK. ALL PERMITS NEED TO INCLUDE THE SAME |
| | LATEST, ACCURATE PLANS. (OCCURS ON SHEETS A1.100 AND |
| | A1.1B1) |
| | |
| | 9) REPEAT COMMENT: SHEET A1.1B1 IS NOT THE LATEST |
| | VERSION OF THIS PLAN SUBMITTED WITH THE RECENT |
| | FOUNDATION PERMIT RESUBMITTAL. ALL PERMITS NEED TO |
| | INCLUDE THE SAME LATEST, ACCURATE PLANS. *** SEE |
| | SETBACK COMMENT ABOVE. |
| | |
| | 10) PLEASE EXPLAIN HOW THE BUILDING INCREASED FROM A |
| | NORTH/SOUTH DIMENSION OF 137 FEET 5 INCHES ON THE |
| | FOUNDATION PLAN TO 137 FEET 9 INCHES ON THE TOWER PLAN |
| | WITHOUT IMPACTING THE SIDE SETBACKS? NOTE THE MINIMUM |
| | SETBACKS MUST BE MAINTAINED. |
| | |
| | 11) REPEAT COMMENT: THE GROUND LEVEL BUILDING PLAN DOES |
| | NOT MATCH THE VERSION APPROVED AS PART OF THE |
| | FOUNDATION PERMIT (LIFE SAFETY) NOR OF THE PLANS |
| | APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT |
| | AMENDMENT. ALL PERMITS NEED TO INCLUDE THE SAME LATEST, |
| | ACCURATE PLANS. NOTE: THE DIMENSION LINES LISTED TO THE |
| | COLUMNS DO NOT ACTUALLY REACH THE COLUMNS. |
| | |
| | 12) REPEAT COMMENT: PROVIDE THE SETBACKS FROM THE FACE |
| | OF GLASS TO THE PROPERTY LINE FOR EACH FLOOR PLAN. THIS |
| | WAS SHOWN ON THE MINOR PLANNED DEVELOPMENT AMENDMENT |
| | PLAN. |
| | |
| | 13) REPEAT COMMENT: THE ELEVATION DRAWINGS DO NOT MATCH |
| | THE ONES APPROVED AS PART OF THE MINOR PLANNED |
| | DEVELOPMENT AMENDMENT. ALL PERMITS NEED TO INCLUDE THE |
| | SAME LATEST, ACCURATE PLANS. |
| | |
| | 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE |
| | PERMITS WITH PLANS: |
| | |
| | A. THE WALLS, FENCES, GATES AND COLUMNS |
| | B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG |
| | PARK ITEMS, BENCHES/PLAZA AREA, ETC. |
| | C. LANDSCAPE |
| | D. IRRIGATION |
| | E. GENERATOR |
| | F. WATER FEATURES |
| | G. PARKING STRIPING |
| | H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE |
| | ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN |
| | PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET |
| | OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE |
| | REQUIRED WITH THE PERMITS. |
| | I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE |
| | ROOM. |
| | J. EV CHARGING STATIONS |
| | |