| 2022-04-04 11:03:41 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21071625 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) PLEASE USE FMC 403.3.1.1 3RD SENTENCE AND TABLE |
| | 403.3.1.1 TO DETERMINE THE OCCUPANCY CLASSIFICATION |
| | USED TO PROVIDE THE OUTDOOR AIR FOR EACH USE OF SPACE. |
| | THE ARCHITECTS EGRESS OCCUPANT COUNT CANNOT BE USED TO |
| | DETERMINE THE OUTDOOR AIR NEEDED FOR THE OCCUPANCY |
| | CLASSIFICATION. PLEASE NAME EACH SPACE PER THE CLOSEST |
| | OCCUPANCY CLASSIFICATION OF TABLE 403.3.1.1 AND PROVIDE |
| | THE OUTDOOR AIR CALCULATIONS USING THE TABLE 403.3.1.1 |
| | AND NOT THE ARCHITECT?S EGRESS OCCUPANT COUNTS. |
| | EXAMPLE: BUSINESS/MEETING COULD BE A CONFERENCE ROOM |
| | WHICH IF USING THE CALCULATIONS IN TABLE 403.3.1.1 |
| | WOULD REQUIRE 149 CFM OF OUTDOOR AIR. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |