| 2022-04-13 15:58:24 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO MEANS TO BACK UP THE GENERATOR IS SHOWN ON THESE | | | PLANS PER 700.3 | | | | | | 2) MAINS NOT LABLED AS 1 OF 6, 2 OF 6 AND SO FORTH. | | | 230.2.(E) PLEASE IDENTIFY ALL MAINS ON RISER DIAGRAM. | | | | | | 3) LOAD CALCULATION ON DWELLING UNITS SHOW A VERY LIGHT | | | LOAD FOR 4 ACS OR 4 HEAT STRIPS IN EACH UNIT. 215.5 | | | | | | 4) PANEL SCHEDULES TO BE MORE SPECIFIC. 408.4(A) A NOTE | | | ON PLAN WILL BE GOOD. | | | | | | 5) PANEL SCHEDULE NOT SHOWN FOR SUB PANELS (EMERGENCY) | | | IN LIVING UNITS. 408.4(A) | | | | | | 6) PLANS NEED TO NOTE SOURCE OF POWER IN ALL PANELS IN | | | ALL UNITS AND OTHER SUB PANELS PER 408.4(B) | | | | | | 7) MAINS 1200 AMPERES OR MORE SHALL BE INSTALLED PER | | | 240.87 FOR ARC ENERGY REDUCTION. 240.87 | | | | | | 8) FIRE PUMP WIRING IS INSTALLED WITH THE OTHER | | | EMERGENCY WIRING, BUT 695.6(A)(2)(A) STATES ALL FIRE | | | PUMP WIRING TO | | | BE KEPT ENTIRELY INDEPENDENT OF OTHER WIRING? | | | | | | 9) FIRE PUMP HAS A 450A BREAKER OR FUSE AHEAD OF THE | | | CONTROLLER? THE SIZE WAS BASED ON WHAT? 695.4? |
|