| 2022-03-28 12:36:32 | NEW COMMERCIAL BUILDING R2 |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) REVISED DRAWINGS LS1.108 AND LS1.107 - THE DOORS |
| | FROM THE UNITS TO THE CORRIDOR LOBBY AND ELEVATOR LOBBY |
| | DO NOT SHOW THE FIRE RATINGS. |
| | |
| | 2) DRAWING A1.105 DIMENSIONS OF THE MASTER BATH TOILET |
| | ROOM IS SHOWN SMALLER THAN THE FHA DRAWING DIMENSIONS |
| | ON DRAWING A1.314 |
| | |
| | 3) PLEASE SHOW THE POOL BARRIER FOR PENTHOUSE POOL FBC |
| | 454.2.17.1 (PRIVATE POOLS ALSO REQUIRE A POOL BARRIER) |
| | |
| | 4) DRAWING LS1.102 AND LS1.103 ELEVATOR R2 SHOULD HAVE |
| | FIRE PROTECTION FROM THE CROSS CORRIDOR - UNLESS THE |
| | ELEVATORS ARE PRESSURIZED PER FBC 3006.3 (PLEASE |
| | PROVIDE A NOTE ON THE DRAWINGS IF THE ELEVATOR |
| | HOISTWAYS ARE PRESSURIZED) |
| | |
| | 5) PLEASE MARK THE FULLY ACCESSIBLE FHA UNIT RESTROOMS |
| | ON DRAWING A1.314 AS "TYPE B" - PLEASE SHOW ON THE |
| | FLOOR PLANS THAT EACH UNIT BATHROOM COMPLIES WITH SPEC. |
| | A OR B - FBC FHA REQUIREMENT 7. (2) |
| | |
| | 6) PLEASE SHOW THE UNIT FLOOR FINISHES - FOR OTHER THAN |
| | CARPET AND PROVIDE THE FOLLOWING ACOUSTICAL TEST |
| | REPORTS - (CAN BE ADDED TO THE DEFERRED SUBMITTAL LIST) |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | 7) (CAN BE ADDED TO THE DEFERRED SUBMITTALS LIST) |
| | PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR |
| | DOORS, ROOFING SYSTEMS, EXTERIOR LOUVERS, EXTERIOR |
| | CLADDING - ETC. - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.3.4 |
| | |
| | 8) PLEASE PROVIDE A DEFERRED SUBMITTALS LIST ON THE |
| | DRAWINGS - - ITEMS SUCH AS WINDOW, DOOR AND ROOFING |
| | PRODUCT APPROVALS, FLOORING/UNDERLAYMENT ACOUSTICAL |
| | TEST REPORTS - ETC. MAY BE DEFERRED SUBMITTALS BY |
| | LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION |
| | DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | |
| | |
| | |