| Date |
Text |
| 2022-01-26 16:00:08 | 01/26/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. ON SHEET 00.002; PAGES ON ARE MISSING FROM THE |
| | PLUMBING INDEX AS FOLLOWS; |
| | |
| | P2.126 |
| | P3.105 |
| | P3.206 |
| | P3.207 |
| | P3.208 |
| | P3.209 |
| | P3.210 |
| | P3.300 |
| | P3.301 |
| | P3.302 |
| | P3.303 |
| | P3.304 |
| | |
| | 2. ON SHEET 00.200, UNDER BUILDING TYPE, IT REFERS TO |
| | FLORIDA BUILDING CODE 2017, WHICH CURRENT IS 2020. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 3. ON SHEET A0.204, UNDER APPLICABLE CODES # 1 AND 2, |
| | IT REFERS TO FLORIDA BUILDING CODE 2017 AND |
| | ACCESSIBILITY 2017, WHICH IS CURRENTLY 2020 7 TH |
| | EDITION. FOR FHA # 5, IF YOU ARE USING THE DESIGN |
| | MANUAL OR THE GUIDELINES, WOULD YOU PLEASE CLARIFY |
| | WHICH SAFE HARBOR. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 4. ON SHEET 00.205; |
| | |
| | A. THE FHA NOTES TALKS ABOUT SPECIFICATION B AND NO |
| | MENTION ON THE LAV TO BE AT 34" PER 7.52 OF THE FHA |
| | DESIGN MANUAL. |
| | |
| | B. THE PENTHOUSE IS A FUTURE BUILD-OUT AND, IN THIS |
| | WAY, ESTABLISHED IN THE BUILDING DEPARTMENT THAT THE |
| | POWDER ROOM IS FOR THE CONSTRUCTION WORKER. WOULD YOU |
| | PLEASE ADD A NOTE OF THIS ON THE PAGE UNDER FAIR |
| | HOUSING ITEM #8 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. ON SHEET 00.206 UNDER LIFE SAFETY # 1 AND 2, IT |
| | REFERS TO FLORIDA BUILDING CODE 2017 AND ACCESSIBILITY |
| | 2017, WHICH IS CURRENTLY 2020 7 TH EDITION. FOR FHA # |
| | 5, IF YOU ARE USING THE DESIGN MANUAL OR THE |
| | GUIDELINES, WOULD YOU PLEASE CLARIFY WHICH SAFE HARBOR. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 6. ON SHEET 00.207; |
| | |
| | A. ON DETAIL C, THE TOILET SEATS NEED TO BE 17 INCHES |
| | TO 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT |
| | PER THE 2020 FBC ACC SEC. 604.4 SEATS. |
| | |
| | B. ON DETAIL C AND F, THE FIXED 18 INCHES FROM THE WALL |
| | IS HAS A MINIMUM AND MAXIMUM PER 2020 FBC ACC SEC. |
| | 604.2 LOCATION. |
| | |
| | C. UNDER GENERAL REQUIREMENTS # 1, 13, 14, 15, 16, IT |
| | REFERS TO FLORIDA BUILDING CODE 2017 AND ACCESSIBILITY |
| | 2017, WHICH IS CURRENTLY 2020 7 TH EDITION. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. ON NUMBER 77, IT REFERS TO THE DISPENSER BEING 12 |
| | AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN |
| | FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF |
| | DISPENSER PER THE 2020 FBC ACC SEC. 604.7. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | E. ON NUMBER 81 WATER CLOSET IN THE ACCESSIBLE RESTROOM |
| | SHALL BE TO THE CENTERLINE OF THE WATER CLOSET 16 |
| | INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL |
| | PER THE 2020 FBC ACC. SEC. 604.2 LOCATION. SEATS OF |
| | WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER 2020 FBC P |
| | 425.3 WATER CLOSET SEATS |
| | |
| | F. UNDER URINAL FOR PARTITION, WOULD YOU PLEASE ADD |
| | THAT THE PARTITIONS TO PROVIDE PRIVACY SHALL EXTEND NOT |
| | LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE |
| | PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS. |
| | |
| | G. FOR THE LABORATORIES, IT SAYS 29 INCHES BUT A |
| | MINIMUM OF 27" KNEE CLEARANCE PER THE 2020 FBC SEC. |
| | 306.3. |
| | |
| | I. GRAB BARS # 95 ON THE REAR NEED TO BE MEASURED TO |
| | THE CENTER OF THE WATER CLOSET TO 12 INCHES TO THE WALL |
| | AND 24 INCHES TO THE OPEN SIDE PER THE 604.5.1 SIDE |
| | WALL AND 604.5.2 REAR WALL. |
| | |
| | 7. ON SHEET 00.210; |
| | |
| | A. UNDER GENERAL REQUIREMENTS, IT HAS BOTH THE |
| | GUIDELINES AND THE DESIGN MANUAL, TWO DIFFERENT SAFE |
| | HARBORS, AND ONLY ONE SHOULD BE NOTED. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? THERE ARE EIGHT |
| | SAFE HARBORS FOR COMPLIANCE WITH THE FAIR HOUSING ACT. |
| | COMPLIANCE WITH ANY ONE OF THE ELEVEN WILL FULFILL THE |
| | FAIR HOUSING ACT?S ACCESS REQUIREMENTS. IF A PARTICULAR |
| | SAFE HARBOR IS CHOSEN FOR USE IN A PARTICULAR PROPERTY, |
| | HOUSING MUST COMPLY WITH ALL OF THE PROVISIONS OF THAT |
| | SAFE HARBOR IN ORDER FOR THERE TO BE A SAFE HARBOR. SO |
| | IT IS UNWISE TO PICK AND CHOOSE AMONG THE PROVISIONS OF |
| | DIFFERENT SAFE HARBOR STANDARDS. |
| | |
| | B. THERE ARE TWO DETAILS, 1 AND 3, AND OTHER FHA |
| | DETAILS THAT ARE NOT NEEDED IN THIS SET OF PLANS. WOULD |
| | YOU PLEASE REMOVE FOR FIELD CLARITY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? THESE IMAGES SEEM TO COME FROM |
| | THE DESIGN MANUAL, BUT THE VERBIAGE UP TOP SEEMS TO BE |
| | ON THE GUIDELINES. PLEASE REFER TO THE ABOVE COMMENT |
| | AND CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. UNDER CHAPTER SIX REQUIREMENTS, IT REFERS TO THE |
| | ANSI 117.1 STANDARD, WHICH IS NOT MENTIONED UNDER |
| | APPLICABLE CODES. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? IT IS IMPORTANT TO NOTE THAT |
| | THE ANSI A117.1 STANDARD CONTAINS ONLY TECHNICAL |
| | CRITERIA, WHEREAS THE FAIR HOUSING ACT, THE |
| | REGULATIONS, AND THE GUIDELINES CONTAIN BOTH SCOPING |
| | AND TECHNICAL CRITERIA. THEREFORE, IN USING ANY OF THE |
| | ANSI STANDARDS, IT IS ALSO NECESSARY TO CONSULT THE ACT |
| | HUD'S REGULATIONS AND THE GUIDELINES. |
| | |
| | D. FOR DETAIL TWO AND 11 ON A0.211 FOR THE SPEC B |
| | BATHROOM USED DOES NOT MATCH THE FLOOR LAYOUT PRESENTED |
| | IN THESE PLANS. FOR EXAMPLE, THE TUB IS DIFFERENT, AND |
| | THERE IS IN THE FHA DESIGN MANUAL REINFORCING FOR GRAB |
| | BARS AT NON-CONVENTIONAL BATHTUBS PAGE 6.10. WOULD YOU |
| | PLEASE PROVIDE DETAIL FOR BACKING PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 8. ON SHEET LS1.100 AND LS1.101 AND ALL OTHERS, THE |
| | APPLICABLE CODES IT HAS THE FLORIDA BUILDING AND |
| | ACCESSIBILITY REFERS TO THE 2017 6 TH EDITION AND THE |
| | CURRENT IS 2020 7 THE EDITION. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? IF YOU ARE USING |
| | THE DESIGN MANUAL OR THE GUIDELINES FOR THE FHA, WOULD |
| | YOU PLEASE CLARIFY WHICH SAFE HARBOR? WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 9. ON SHEET A1.1B1, |
| | |
| | A. LEVEL B1 IN THE BREAK ROOM, PLEASE SHOW THE CLEAR |
| | FLOOR SPACE FOR THE SINK PER THE 2020 FBC ACC SEC. |
| | 602.2. |
| | |
| | B. LEVEL B2, THE PUMPROOM DOES NOT SHOW A FLOOR DRAIN, |
| | AND IT IS NOT REQUIRED BUT RECOMMENDED. WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN STAIRCASE C, THERE IS A FLOOR DRAIN WITH NUMBER |
| | 04 POINTING TO IT AND NOT LABELED. WOULD YOU PLEASE |
| | CLARIFY OR CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 10. ON SHEET A-100; |
| | |
| | A. THE PLANTER SHOW DRAIN BUT NOT LABELED. WOULD YOU |
| | PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE LABEL ALL ROOMS AND FLOOR DRAIN PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. IN. THE MEN'S RESTROOM DOES NOT SHOW THE WATER |
| | CLOSET. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | D. IN THE EMPLOYEE RR, THE FIXTURES ARE MISSING. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | E. THE GENERATOR IS SHOWN, AND IT SHOULD BE NOTED THAT |
| | IT IS BELOW B1. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | F. WOULD YOU PLEASE SHOW ALL CLEAR FLOOR SPACE PER THE |
| | FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE. |
| | PLEASE INDICATE THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR |
| | FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. LAV IN THE OPEN |
| | AREA ON THE WOMEN'S REQUIRES CLEAR FLOOR SPACE. |
| | |
| | 11. ON SHEET A-101; |
| | |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | WOMEN'S RESTROOM FOR THE LAV ON THE OPEN AREA PER THE |
| | 2020 FBC ACC SEC. 602.2. PLEASE INDICATE THE CLEAR |
| | FLOOR SPACE DIAGRAM AND DIMENSIONS PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | B. IN THE JANITOR'S ROOM, THE SERVICE SINK (MOP SINK) |
| | SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE |
| | IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2 |
| | AND 2020 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS |
| | SHEET. |
| | |
| | 12. ON SHEET A-102; |
| | |
| | A. IN THE WARMING KITCHEN, THERE IS S SINK. WOULD YOU |
| | PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC |
| | SEC. 602.2. PLEASE INDICATE THE CLEAR FLOOR SPACE |
| | DIMENSIONS PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR |
| | FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE LABEL THE JANITOR SINK PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. IN THE MEN'S RESTROOM, THERE IS A LAV IN THE OPEN |
| | AREA THAT REQUIRES CLEAR FLOOR SPACE PER THE 2020 FBC |
| | ACC SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | 13. ON SHEET A-103; |
| | |
| | A. ON THE GUEST ROOM #2 BATH SHOWER DOES NOT COMPLY |
| | WITH THE 2020 FBC ACC SEC. 608.2. SHOWER COMPARTMENTS. |
| | PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. HOW WILL THE GRAB BARS |
| | COMPLY PER THE 2020 FBC ACC SEC. 608.2. PLEASE SHOW THE |
| | TURNING RADIUS SPACE OF FIVE FEET 603.2.1, 304.3.1 |
| | CIRCULAR SPACE. |
| | |
| | B. IN WOMEN'S AND MEN'S SPAS, THE OPEN LAVS NEED TO |
| | SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC SEC. |
| | 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | C. THE MEN'S RESTROOM NEEDS TO COMPLY WITH THE 2020 |
| | ACCESSIBILITY AND SHOW THE CLEAR FLOOR SPACE FOR LAV, |
| | TURNING RADIUS, AND TOILET. THE WOMAN'S RESTROOM NEEDS |
| | TO SHOW THE TURNING SPACE PER THE 2020 FBC ACC SEC. |
| | 612.3 TURNING SPACE. |
| | |
| | D. THE MEN'S AND WOMAN'S SAUNA AND STEAM NEED TO SHOW |
| | THE TURNING SPACE PER THE 2020 FBC ACC SEC. 612.3 |
| | TURNING SPACE. |
| | |
| | E. THE TREATMENT ROOM NEEDS TO SHOW THE LAVS CLEAR |
| | FLOOR SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR |
| | FLOOR SPACE. |
| | |
| | 14. ON SHEET A1.104, 105, AND 124; |
| | |
| | A. WOULD YOU PLEASE IDENTIFY THE FHA UNITS AND SHOW THE |
| | CLEAR FLOOR SPACE FOR LAV, SHOWER, TUB, AND TOILET PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. IT IS SAID THAT SPECIFICATION B IS TO BE USED IN THE |
| | MASTER, SO PLEASE TELL US HOW THE FHA GRAB BAR BACKING |
| | WILL COMPLY SINCE IT IS AN OPEN SHOER TO TWO SIDES. |
| | WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 15. ON SHEET A1.124, THE BUILD-OUT IS FOR THE FUTURE. |
| | WOULD YOU PLEASE PROVIDE A NOTE ON THIS PAGE STATING |
| | THE FHA BATHROOM AND ITS COMPLIANCE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 16. ON SHEET A1.125; |
| | |
| | A. IN THE POOL EQUIPMENT, THERE IS A SINK AND A HOSE |
| | BIBB. WOULD YOU PLEASE LABEL PER THE SOLAR COVER |
| | REQUIRED PER 2020 FBC RE 403.10.3? |
| | |
| | B. THERE IS A GAS GRILL; PLEASE IDENTIFY TANK PROPANE |
| | OR A GAS SYSTEM PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. UNDER ROOF GENERAL NOTES, THERE IS MENTION FOR ROOF |
| | DRAIN AND OVERFLOW CALCULATION. WOULD YOU PLEASE |
| | PROVIDE THE PAGE NUMBER WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 17. ON SHEET A1.204, 205, 206, 207, 208, 209, 210, 300, |
| | 301, 302, 303, AND 304, PLEASE IDENTIFY THE BATHROOM |
| | WHICH IS THE FHA AND SHOW CLEAR FLOOR SPACE FOR ALL |
| | FIXTURES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. WOULD YOU PLEASE |
| | PROVIDE DIMENSIONS FOR FIXTURES PER THE 2020 FBC SEC. |
| | 405.3.1. |
| | |
| | 18. ON SHEET A1.306; |
| | |
| | A. THE SHOWER IS SHOWN AT 2'-11", AND IT SHALL HAVE |
| | SIZES AND CLEARANCES COMPLYING WITH 2020 FBC ACC SEC. |
| | 608.2. |
| | |
| | B. WOULD YOU PLEASE SHOW A CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSIONS FOR ALL FOUR SHOWERS PER THE 2020 FBC |
| | ACC SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | C. WOULD YOU PLEASE SHOW OR POINT TO THE PAGE WHICH THE |
| | SEAT REINFORCES VERTICAL OR HORIZONTAL FORCE OF 250 |
| | POUNDS IS APPLIED AT ANY POINT ON THE SEAT, FASTENER, |
| | MOUNTING DEVICE, OR SUPPORTING STRUCTURE PER THE 2020 |
| | FBC ACC SEC. 610.4 STRUCTURAL STRENGTH. |
| | |
| | D. ON DETAIL #3, WOULD YOU PLEASE SHOW THE GRAB BARS TO |
| | THE TOP OF THE GRIPPING SURFACE PER THE 2020 FBC ACC |
| | SEC. 609.4. |
| | |
| | E. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 19. ON SHEET A1.306A; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE SHOW A CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSIONS FOR THE SINK PER THE 2020 FBC ACC SEC. |
| | 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | C. WOULD YOU PLEASE SHOW THE SINK OF 34 INCHES MAXIMUM |
| | PER THE 2020 FBC ACC SEC. 606.3. |
| | |
| | 20. ON SHEET A1.307; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL # 4, 9, AND 10, WOULD YOU PLEASE SHOW THE |
| | GRAB BARS TO THE TOP OF THE GRIPPING SURFACE PER THE |
| | 2020 FBC ACC SEC. 609.4. |
| | |
| | C. UNDER URINAL FOR PARTITION, WOULD YOU PLEASE ADD |
| | THAT THE PARTITIONS TO PROVIDE PRIVACY SHALL EXTEND NOT |
| | LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE |
| | PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS. |
| | |
| | 21. ON SHEET A1.308; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN WOMEN'S AND MEN'S SPAS, THE OPEN LAVS NEED TO |
| | SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC SEC. |
| | 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | 22. ON SHEET A1.309; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV, |
| | AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 |
| | CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 23. ON SHEET A1.310; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV, |
| | AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 |
| | CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. THE OPEN |
| | LAV REQUIRES CLEAR FLOOR SPACE PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | 24. ON SHEET A1.311; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV, |
| | AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 |
| | CLEAR FLOOR SPACE AND WPB |
| | |
| | 25. ON SHEET A1.312, IT SAYS FOR ADA FIXTURES AND |
| | ACCESSORIES, REFER TO A0.004 AND A0.005 AND NO SUCH |
| | PAGE. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | 26. ON SHEET A1.313; |
| | |
| | A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO |
| | A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV, |
| | AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 |
| | CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. THE GUEST ROOM #2 BATH SHOWER DOES NOT COMPLY WITH |
| | THE 2020 FBC ACC SEC. 608.2. SHOWER COMPARTMENTS. |
| | PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. HOW ARE THE GRAB BARS |
| | GOING TO COMPLY PER THE 2020 FBC ACC SEC. 608.2. PLEASE |
| | SHOW THE TURNING RADIUS SPACE OF FIVE FEET 603.2.1, |
| | 304.3.1 CIRCULAR SPACE. |
| | |
| | 27. ON SHEET A1.314; |
| | |
| | A. ON THIS PAGE HAS FHA PLANS FOR THE DIFFERENT |
| | RESTROOMS, BUT SHEET 00.205 SAYS THE MASTER BEDROOM TO |
| | BE SPECIFICATION B. WHICH ONE IS THE CORRECT ONE, AND |
| | WOULD YOU LABEL THE ONE PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. ONE OF EACH TYPE OF FIXTURE MUST BE USABLE BY A |
| | PERSON WITH A DISABILITY IN A SPECIFICATION B BATHROOM |
| | PER THE FHA PAGE 7.34. |
| | |
| | C. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE TO THE |
| | WATER CLOSET PER THE FHA PAGE 7.43 AND THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON DETAIL # 5 ON THE SHOWER, WHERE ARE THE GRAB BARS |
| | SUPPORTS FOR THE SIDE AND SHOW THE BACKING FOR FRONT |
| | AND BACK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SHOW THE CLEAR |
| | FLOOR SPACE FOR THE TUB AND WATER CLOSET PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. ONLY ON LAV SHALL COMPLY ON |
| | SPECIFICATION B. |
| | |
| | E. ON DETAIL # 6, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE TO THE WATER CLOSET PER THE FHA PAGE 7.43 AND THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | F. ON DETAIL # 7, IT SHOWS THE CLEAR FLOOR SPACE TO THE |
| | WATER CLOSET BUT CAN YOU SHOW DIMENSIONS PER THE FHA |
| | PAGE 7.43 AND THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. FOR THE |
| | SHOWER, WHERE ARE THE GRAB BARS SUPPORTS FOR THE SIDE, |
| | AND PLEASE SHOW THE BACKING FOR FRONT AND BACK PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SHOW THE CLEAR FLOOR SPACE FOR |
| | THE TUB AND WATER CLOSET PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ONLY ON LAV SHALL COMPLY ON SPECIFICATION B. |
| | |
| | G. ON DETAIL # 8, SHOW THE BACKING FOR SIDE, FRONT, AND |
| | BACK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SHOW THE CLEAR |
| | FLOOR SPACE FOR THE TUB PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SHOWS THE CLEAR FLOOR SPACE TO THE WATER CLOSET, TUB, |
| | AND SHOWER WITH DIMENSIONS PER THE FHA PAGE 7.43 AND |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 28. ON SHEET A1.400, IN THE EMPLOYEE RR, WOULD YOU |
| | PLEASE SHOW THE TURNING SPACE PER THE 2020 FBC ACC SEC. |
| | 612.3 TURNING SPACE. |
| | |
| | 29. WOULD YOU PLEASE A PLUMBING PLAN INCLUDING THE |
| | SANITARY, CONDENSATE, STORM, AND WATER ISOMETRIC |
| | DRAWINGS PER THE WPB AMEND TO FBC 107.3.5.1.3(13). |
| | |
| | 30. ON SHEET P2.1B2; |
| | |
| | A. WOULD YOU PLEASE SHOW THE INDIRECT CONNECTION FOR |
| | THE ELEVATOR TO THE SANITARY ON THE PLUMBING DETAILS |
| | AND GIVE A REFERENCE PAGE NUMBER FOR IT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE LABEL THE STAIR WELL AND ELEVATOR |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. IT IS MOTION ON PLANS HOW THE PIPES SHALL BE |
| | PROTECTED WATER LINES AND SANITARY WHERE THE VEHICULAR |
| | PATHWAY IN THE PARKING GARAGE EXPOSED TO DAMAGE AND |
| | SHALL BE RECESSED INTO THE WALL OR OTHERWISE PROTECTED |
| | IN AN APPROVED MANNER PER 2020 FBC SEC. P 305.7 |
| | PROTECTION OF COMPONENTS OF THE PLUMBING SYSTEM. PLEASE |
| | PROVIDE DETAILS OR SHOW BOLLARDS IN FRONT OF PIPES PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | WOULD YOU INCORPORATE A NUMBER ON THE LEGEND PRESENT |
| | FOR THE BOLLARD LOCATION AND SHOW IT ON B1 AND B2 PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 31. ON SHEET P2.1B1; |
| | |
| | A. IT IS MOTION ON PLANS HOW THE PIPES SHALL BE |
| | PROTECTED WATER LINES AND SANITARY WHERE THE VEHICULAR |
| | PATHWAY IN THE PARKING GARAGE EXPOSED TO DAMAGE AND |
| | SHALL BE RECESSED INTO THE WALL OR OTHERWISE PROTECTED |
| | IN AN APPROVED MANNER PER 2020 FBC SEC. P 305.7 |
| | PROTECTION OF COMPONENTS OF THE PLUMBING SYSTEM. PLEASE |
| | PROVIDE DETAILS OR SHOW BOLLARDS IN FRONT OF PIPES PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | WOULD YOU INCORPORATE A NUMBER ON THE LEGEND PRESENT |
| | FOR THE BOLLARD LOCATION AND SHOW IT ON B1 AND B2 PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE ARE TWO RPZ'S AND AN FD IN A ROOM. WOULD YOU |
| | PLEASE LABEL THE ROOM PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. THERE IS A RESTROOM NEXT TO THE SERVICE CORRIDOR, |
| | THE EMPLOYEE RESTROOM THAT IS NOT LABELED, AND THE |
| | LAUNDRY ROOM. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | D. WOULD YOU, PLEASE LABEL THE DRAIN IN THE EMPLOYEE |
| | RESTROOM AND THE LAUNDRY ROOM PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | E. WHERE THE FOUR SHOWERS ARE, WOULD YOU PLEASE LABEL |
| | THE BREAKROOM, W, AND M LOCKER ROOM PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | F. IN STAIRWELL C, THE SECONDARY STAIRS THAT GO OUTSIDE |
| | LOOK LIKE A DRAIN AT THE BOTTOM. WOULD YOU PLEASE LABEL |
| | ALL STAIRWELLS AND IDENTIFY DRAINS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 32. ON SHEET P2.101; |
| | |
| | A. THERE ARE DRAINS IN THE FIRE PUMP AND NEXT TO THE |
| | TRASHING STAGE THAT IS NOT LABELED. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE LABEL THE ROOMS NEXT TO THE TRASH |
| | STAGING ARE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM |
| | ARE NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN |
| | THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE |
| | THAT LIMITS THE BETWEEN THE SOURCE AND THE OUTLET; |
| | PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM ALLOWABLE |
| | PIPE LENGTH METHOD AND SIZE ACCORDANTLY. THE COMMENT |
| | WILL APPLY TO ALL AND WHERE THERE IS A LOOP SYSTEM. |
| | |
| | 33. ON SHEET P2.102; |
| | |
| | A. THE RESTROOM NEXT TO THE ELEVATOR IS NOT LABELED. |
| | WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. DOES THE KITCHEN HAVE AN ICEMAKER OR COFFEE MAKER, |
| | AND IF SO, IT SHALL BE EQUIPPED WITH AN IN-LINE VACUUM |
| | BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC |
| | SEC. 608.13.10. |
| | |
| | C. THERE IS A SHOWER FOR THE POOL IS THE DRAIN GOING IN |
| | A STORM OR TO A DRY WELL. IF RAIN IS COLLECTED, IT |
| | CANNOT GO INTO THE SANITARY. WOULD YOU PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 34. ON SHEET P2.103, THERE IS A DRINKING FOUNTAIN IN |
| | FRONT OF THE BUSINESS ROOM. WHAT IS THE DISTANCE TO THE |
| | GYM PER THE 2020 FBC SEC. P 403.5 DRINKING FOUNTAIN |
| | LOCATION. |
| | |
| | 35. ON SHEET P2.104 AND P2.124, WOULD YOU PLEASE LABEL |
| | ALL RESTROOMS, BEDROOMS, AND AMENITY ROOMS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 36. ON SHEETS P3.105, P3.204, P3.205, P3.206, P3.207, |
| | P3.208, P3.209, P3.210, P3.300, P3.301, P3.302, P3. 303 |
| | AND P3.304 WOULD YOU PLEASE LABEL ROOMS AND RESTROOM |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 37. ON SHEET P4.201; |
| | |
| | A. WOULD YOU PLEASE LABEL THE ROOM AND SHOW THE |
| | SANITARY PIPE FOR THEM PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | C. WOULD YOU PLEASE LABEL THE FLOOR DRAIN IN THE |
| | RESTROOM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 38. ON SHEET P5.101; |
| | |
| | A. WOULD YOU PLEASE PROVIDE SHUTOFF VALVES ON EACH |
| | RISER PER THE 2020 FBC SEC. 606.1 (4). |
| | |
| | B. IT SHOWS A DOUBLE CHECK VALVE AS BACKFLOW AND |
| | REDUCED PRESSURE ZONE VALVE REQUIRED PER THE CITY OF |
| | WEST PALM BEACH AND THE CROSS CONNECTION PROGRAM. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 39. ON SHEET P5.103; |
| | |
| | A. RISER 1 SHOWS THE L-3, SH-3 AND WC-3 ARE VENTED |
| | INCORRECTLY TWICE PER THE 2020 FBC SEC. P 901.2. |
| | |
| | B. RISER 2 SHOWS THE DF-1 AND WASHERS ARE VENTED |
| | INCORRECTLY PER THE 2020 FBC SEC. P 901.2. |
| | |
| | C. FOR RISER 2, THE CONTINUATION FOR LETTER F SAYS |
| | P4.505 THAT PAGE DOES NOT EXIST. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. ON RISER 2, THERE IS A FLOOR DRAIN AND WATER CLOSET |
| | TOGETHER, AND A VENT IS REQUIRED PER THE 2020 FBC SEC. |
| | 910.1 INDIVIDUAL VENTS PERMITTED. |
| | |
| | E. ON RISER 2, THERE IS A VENT WITH NO CONTINUATION |
| | POINT ON THE GROUND FLOOR AND ON B2 AS WELL. WOULD YOU |
| | PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 40. ON SHEET P5.104; |
| | |
| | A. THE DRAIN PAN IS SHOWN GOING INTO THE SANITARY ON 4 |
| | TH, AND 5 TH DOES THIS DRAIN CARRY CONDENSATE. WOULD |
| | YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. THE 4 TH FLOOR SHOWS 4 SH 2, 1 SH 1, 1 DP, 1 B-1, 4 |
| | WC-2, AND 1 WC-1 THAT ARE NOT VENTED AND ON THE MAIN |
| | DRAIN BY THE STACK. WOULD YOU PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 41. ON SHEET P5.106; |
| | |
| | A. THE CLEANOUTS ARE REQUIRED IN THE BOTTOM OF THE |
| | STACK PER THE 2020 FBC SEC. P 1101.8 CLEANOUTS |
| | REQUIRED. |
| | |
| | B. AT GROUND LEVEL, IT SAT TP PODIUM PLATER DRAINAGE. |
| | WOULD YOU PLEASE GIVE THE CORRESPONDING PAGE NUMBER PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 42. ON SHEETS, P5.106 AND P5.107 SHOW THE TABLES USED |
| | FOR THE SIZING OF THE STORM PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 43. ON SHEET P5.107, LETTERS A, B, AND C REFER TO |
| | CONTINUATION FOR P5.06 AND NO SUCH PAGE. WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 44. ON SHEET P7.102; |
| | |
| | A. PLEASE PROVIDE DETAIL ON RIGID SUPPORT SWAY BRACING |
| | SHALL BE PROVIDED AT CHANGES IN A DIRECTION MORE |
| | SIGNIFICANT THAN 45 DEGREES FOR PIPE SIZES 4 INCHES AND |
| | LARGER PER FBC-PLUMBING SEC. 308.6. SUBMIT DETAILS FOR |
| | THE BRACING. |
| | |
| | B. ON DETAIL 4 FOR THE CONDENSATE DRAIN, WOULD YOU |
| | PLEASE PROVIDE THE LOCATION WHERE THE DRAIN WILL BE |
| | DISCHARGING PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON |
| | ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU |
| | LIKE TO PREVENT FURTHER REVIEWS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |