| 2022-01-10 15:22:18 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21071625 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| | GENERATOR WILL REQUIRE A SEPARATE PERMIT AND PLAN |
| | REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THAT THE CARBON MONOXIDE AND NITROGEN |
| | DIOXIDE DETECTORS ARE SEPARATE PIECES OF EQUIPMENT AND |
| | SHOW THE MOUNTING HEIGHTS OF EACH PIECE OF EQUIPMENT |
| | ACCORDING TO FBC M 404.1. PLEASE PROVIDE A DRAWING |
| | SHOWING THE LOCATIONS OF EACH CARBON MONOXIDE AND |
| | NITROGEN DIOXIDE LOCATION PER THE MANUFACTURER?S |
| | INSTRUCTIONS. FBC 107.2.1 |
| | |
| | 3) SHEET LS1.100 INDICATES FIRE RATED WALLS IN SEVERAL |
| | LOCATIONS ON BOTH LEVELS OF THE PARKING GARAGE. PLEASE |
| | SHOW THE REQUIRED PENETRATION PROTECTION AT ALL |
| | DUCTWORK PENETRATING THESE RATED WALLS. FBC M 607 |
| | |
| | 4) SHEET M2.1B1D: PLEASE SHOW HOW MANY DRYERS ARE IN |
| | THE LAUNDRY ROOM, ALSO PLEASE PROVIDE A DETAIL OF THE |
| | DRYER DUCT TERMINATION LOCATION. FBC 504 |
| | |
| | 5) SHEET M2.1B1D: THE DRYER DUCTS ARE PENETRATING RATED |
| | WALLS, PLEASE PROVIDE PROTECTION FOR THESE |
| | PENETRATIONS. FBC M 607 |
| | |
| | 6) THE MAKEUP AIR FOR THE LAUNDRY ROOM, STORAGE AND |
| | EQUIPMENT ROOM CANNOT BE TAKEN FROM THE GARAGE. |
| | |
| | 7) SHEET M2.1B1D: NOTE 4 OF THE CODE NOTES INDICATES A |
| | MAKEUP AIR PLENUM ON THE ARCHITECTURAL DRAWINGS, PLEASE |
| | REFERENCE THE SHEET NUMBER OF THE ARCHITECTURAL DRAWING |
| | THAT HAS THIS INFORMATION. |
| | |
| | 8) SHEET M2.1B1P: PLEASE PROVIDE PIPE SIZES FOR THE |
| | PIPING ON THE PIPING PLAN. |
| | |
| | 9) PLEASE SHOW THE REQUIRED FIRE DAMPERS ON THE |
| | DRAWINGS WHERE THE DUCTWORK IS PENETRATING ALL RATED |
| | WALLS. FBC M607 |
| | |
| | 10) PLEASE SHOW OUTDOOR AIR DAMPERS IN THE OUTDOOR AIR |
| | DUCTWORK. |
| | |
| | 11) THE PFSF?S DUCTWORK ARE PENETRATING A RATED WALL, |
| | PLEASE PROVIDE A DETAIL OF HOW THIS PENETRATION WILL BE |
| | PROTECTED. FBC M 607 |
| | |
| | 12) PLEASE SHOW THE SMOKE DETECTORS INSIDE THE SUPPLY |
| | DUCTWORK ACCORDING TO FBC M 606.2.2 |
| | |
| | 13) PLEASE REVISIT THE OUTDOOR AIR CALCULATIONS |
| | PROVIDED AS IT APPEARS THAT SOME HAVE A LOWER OCCUPANT |
| | COUNT THAN WHAT FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | ALLOWS. |
| | |
| | 14) SHEET M6.101: THE AIR DEVICE SCHEDULE STOPS AT |
| | DESIG. M, PLEASE SHOW INFORMATION FOR THE DESIG. P. FBC |
| | 107.2.1 |
| | |
| | 15) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZING |
| | AND TERMINATION LOCATION. FBC M 307 |
| | |
| | 16) SHEET M5.101: PLEASE IDENTIFY AND INCLUDE |
| | SPECIFICATIONS FOR THE EXHAUST FANS FOR THE DRYER |
| | EXHAUST. |
| | |
| | 17) PLEASE PROVIDE SPECIFICATIONS FOR THE LAUNDRY |
| | DRYERS INCLUDING THE DUCT LENGTH. FBC M 504 |
| | |
| | 18) PLEASE PROVIDE A DETAIL SHOWING THE DUCT SUPPORTS |
| | IN THE SHAFTS. FBC M 305 |
| | |
| | 19) SHEET M5.103: PLEASE SHOW THE SPF FOR STAIR B |
| | PRESSURIZATION ON THIS RISER DETAILS. |
| | |
| | 20) SHEET M8.101: THE GARAGE CARBON MONOXIDE/NITROGEN |
| | DIOXIDE SUPPLY/EXHAUST FAN CONTROL SEQUENCE MUST MATCH |
| | FBC M 404.1- 1 AND 2 |
| | |
| | 21) SHEET M2.101D: PLEASE SHOW THAT THE EF-3 IS A |
| | CORROSION RESISTANT FAN BECAUSE OF IT?S LOCATION IN THE |
| | POOL EQUIPMENT ROOM. |
| | |
| | 22) PLEASE SHOW THAT ALL EXHAUST TERMINATION LOCATIONS |
| | MEET THE 3 FOOT CLEARANCE FROM OPERABLE OPENINGS INTO |
| | THE BUILDING. FBC M 501.3 |
| | |
| | 23) FBC M2.125D: PLEASE SIZE THE DUCTWORK ON THE ROOF |
| | FROM THE SHAFT TO THE DOAS-1 INCLUDING THE DUCT SIZE TO |
| | THE CSEF-1. FBC 107.2.1 |
| | |
| | 24) PLEASE SHOW DUCT SIZES FOR THE DUCT BOXES LEAVING |
| | THE FCU?S. FBC 107.2.1 |
| | |
| | 25) COMMON EXHAUST SYSTEM FOR CLOTHES DRYERS LOCATED IN |
| | MULTISTORY STRUCTURES MUST MEET THE REQUIREMENTS OF |
| | 504.10 1-12. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |