| 2022-01-24 12:23:59 | 01/24/22 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P5.108 AND P5.109; |
| | |
| | A. ON THE CODE NOTES AND 2ND FLOOR NOTE, IT SAYS 2017 |
| | FLORIDA FUEL GAS CODE, AND THE CURRENT IS 2020 FG 7 TH |
| | EDITION PER THE WPB AMENDMENTS TO FBC 102.3 APPLICATION |
| | OF REFERENCES. |
| | |
| | B. FOR LETTERS A, C, AND D, IT SAYS P5.09 AND NO SUCH |
| | PAGE. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | C. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | D. WOULD YOU PLEASE A PLUMBING PLAN INCLUDING A GAS |
| | ISOMETRIC DRAWING PER THE WPB AMEND TO FBC |
| | 107.3.5.1.3(13). |
| | |
| | E. WOULD YOU PLEASE SUBMIT THE LENGTH OF ALL PIPE CUT |
| | SECTIONS ON THE ISOMETRIC DRAWING PER 2020 FBC FG SECS. |
| | 402.4.1, 402.4.2. |
| | |
| | F. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | G. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2020 FBC FG |
| | SEC. 409.4. |
| | |
| | H. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FG SECS. |
| | 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH |
| | 402.4 (37). |
| | |
| | I. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2020 FBC FG SEC. 402.4.1. |
| | |
| | J. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| | 305.1. |
| | |
| | K. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC FG SECS. 402.2 AND 301.3. |
| | |
| | L. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED FOR THE GRILL AND THE PIPE SIZE PER THE |
| | WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | M. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG |
| | SEC. 410.1. |
| | |
| | N. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC |
| | 410.2. |
| | |
| | O. WOULD YOU, PLEASE LABEL THE SHUTOFF VALVE ON GAS |
| | ISOMERIC PER THE 2020 FBC FG SEC. 409.5. |
| | |
| | P. WOULD YOU PLEASE SHOW DRIP LEG ON EQUIPMENT |
| | INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD |
| | GRILLS PER THE 2020 FBC FG 408.2. |
| | |
| | Q. WOULD YOU PLEASE SUBMIT COMBUSTION AIR CALCULATIONS |
| | FOR THE GAS APPLIANCES ON 2ND, GROUND, AND B1 LEVEL. |
| | WHERE DOES THE BUILDING?S MECHANICAL VENTILATION SYSTEM |
| | PROVIDE COMBUSTION AIR? THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR PER THE 2020 FBC FG SEC. |
| | 304.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR |
| | SYSTEM. |
| | |
| | R. WOULD YOU PLEASE SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER THE 2020 FBC FG SEC. 304.1, 614.5 (CLOTHES |
| | DRYERS), |
| | |
| | S. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS |
| | SYSTEM TO BE PURGED AND ADMINISTERED BY A CITY |
| | INSPECTOR. BEFORE DOING THIS PROCESS, PLEASE HAVE A |
| | DESCRIPTION OF HOW THE PURGE WILL TAKE PLACE AND WHEN |
| | SUBMITTED TO THE CHIEF PLUMBING INSPECTOR IN ADVANCE. |
| | WOULD YOU PLEASE CALL 561-805-6692 FOR FURTHER |
| | CLARIFICATION? |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |