| 2021-12-27 13:50:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS1 - 102 - THE OUTDOOR AMENITY DECK INDICATES |
| | A SET OF DOUBLE DOORS OUTSWINGING ALONG THE EGRESS |
| | ROUTE. THESE DOUBLE DOORS ARE REQUIRED TO SWING IN THE |
| | DIRECTION OF EGRESS. |
| | |
| | NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPANCIES, |
| | AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF AN ELECTIRC FIRE PUMP AND A |
| | GENERATOR; HOWEVER, THERE IS NO INDICATON THAT THE |
| | ELECTRIC FIRE PUMP WILL BE POWERED BY THE GENERATOR IN |
| | THE EVENT OF LOSS OF POWER. |
| | |
| | PER NFPA 20 |
| | |
| | 9.3 ALTERNATE POWER. |
| | 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT |
| | LEAST |
| | ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE |
| | THE |
| | HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY |
| | OF THE |
| | FIRE DEPARTMENT APPARATUS. |
| | 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT |
| | DESCRIBED IN |
| | 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE |
| | PROVIDED |
| | WHERE THE NORMAL SOURCE IS NOT RELIABLE. |
| | 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE |
| | PUMP |
| | SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE |
| | PUMP, |
| | BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP |
| | ELECTRIC |
| | MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE |
| | MEETING |
| | 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS STANDARD. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO |
| | COMPLY ON SHEET FP 11. |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF A BDA SYSTEM |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, AS OUR RADIOS OPERATE ON |
| | THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | THERE IS NO WAY TO DETERMINE IF YOUR BUILDING WOULD |
| | NEED IT OR NOT WITHOUT PROPER TESTING. |
| | |
| | SHOULD YOUR BUILDING NOT PASS THE TESTING/SURVEY, AN |
| | AMPLIFICATION SYSTEM WOULD BE REQUIRED. |
| | |
| | SHOULD YOUR BUILDING PASS THE TESTING/SURVEY I WOULD |
| | COME IN WITH OUR PORTABLE RADIOS AND CONDUCT AN |
| | OPERATIONAL TEST TO CONFIRM. IF THE PORTABLE RADIO TEST |
| | FAILS AN AMPLIFICATION SYSTEM IS REQUIRED. |
| | |
| | THE OWNER/CONTRACTOR WOULD BE RESPONSIBLE TO CONDUCT |
| | THE TESTING/SURVEY BY A QUALIFIED THIRD PARTY. |
| | |
| | A BDA PERMIT IS REQUIRED SEPARATE FROM ANY OTHER |
| | PERMIT. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO |
| | COMPLY ON SHEET LS 100. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF FIRE ALARM DEVICES ON THE |
| | ELECTRICAL PLAN SHEETS. |
| | |
| | ALL FIRE ALARM WORK SHALL BE INSTALLED UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO |
| | COMPLY ON SHEETS E0 .001 & LS 100. |
| | |
| | |
| | |
| | |
| | 5) THERE ARE INDICATIONS ON THE CIVIL SHEETS OF |
| | UNDEGROUND FIRE LINES, INCLUDING THE FDC & DDCV. |
| | |
| | ALL FIRE LINE UNDERGROUND WORK INCLUDING THE FDC & DDCV |
| | SHALL INSTALLED PER NFPA 24 AND UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS . |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT OF |
| | SHEET C. |
| | |
| | |
| | |
| | 6) THERE ARE INDICATIONS OF ELEVATOR FOYERS/LOBBIES TO |
| | INDIVIDUAL UNITS WITH NO CLEAR EXIT ACCESS TO AN EXIT. |
| | |
| | PER NFPA 101 |
| | |
| | 7.2.1.6.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES |
| | LOCKING. |
| | WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR |
| | ASSEMBLIES SEPARATING |
| | THE ELEVATOR LOBBY FROM THE EXIT ACCESS REQUIRED BY |
| | 7.4.1.6.1 SHALL BE PERMITTED |
| | TO BE ELECTRICALLY LOCKED, PROVIDED THAT ALL THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE ELECTRICAL LOCKING HARDWARE IS LISTED IN |
| | ACCORDANCE WITH |
| | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| | (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE |
| | ALARM SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.6. |
| | (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7. |
| | (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY |
| | 7.2.1.6.3(3) IS |
| | ARRANGED TO INITIATE THE BUILDING FIRE ALARM SYSTEM. |
| | (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED, |
| | SUPERVISED SMOKE |
| | DETECTION SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| | (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED |
| | BY |
| | 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING FIRE |
| | ALARM SYSTEM |
| | AND NOTIFY BUILDING OCCUPANTS. |
| | (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY |
| | OTHER THAN MANUAL |
| | FIRE ALARM BOXES UNLOCKS THE ELECTRICAL LOCKS ON THE |
| | ELEVATOR LOBBY |
| | DOOR ASSEMBLY. |
| | (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRICAL LOCK |
| | SYSTEM UNLOCKS |
| | THE ELECTRICAL LOCKS ON THE ELEVATOR LOBBY DOOR |
| | ASSEMBLIES. |
| | (9) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES |
| | REMAIN ELECTRICALLY |
| | UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM HAS BEEN |
| | MANUALLY RESET. |
| | (10) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN |
| | MECHANICALLY |
| | LATCHED AFTER BEING ELECTRICALLY UNLOCKED, |
| | LATCH-RELEASING HARDWARE |
| | IN ACCORDANCE WITH 7.2.1.5.10 IS AFFIXED TO THE DOOR |
| | LEAVES. |
| | (11) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR |
| | COMMUNICATION |
| | BETWEEN THE ELEVATOR LOBBY AND A CENTRAL CONTROL POINT |
| | THAT |
| | IS CONSTANTLY STAFFED. |
| | (12) THE CENTRAL CONTROL POINT STAFF REQUIRED BY |
| | 7.2.1.6.3 IS CAPABLE, |
| | TRAINED, AND AUTHORIZED TO PROVIDE EMERGENCY |
| | ASSISTANCE. |
| | (13) THE PROVISIONS OF 7.2.1.6.1 FOR DELAYED-EGRESS |
| | ELECTRICAL LOCKING |
| | SYSTEMS ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR |
| | ASSEMBLIES. |
| | (14)* THE PROVISIONS OF 7.2.1.6.2 FOR SENSOR-RELEASE OF |
| | ELECTRICAL LOCKING |
| | SYSTEMS ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR |
| | ASSEMBLIES. |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAILED SEQUENCE OF |
| | OPERATION/USE FOR EACH OF THE VARIOUS FOYER/SECONDARY |
| | VESTIBULE FLOOR PLANS THAT COMPLIES WITH THE ABOVE |
| | CODE. |
| | |
| | |
| | 7) THERE IS NO RATIONAL ANALYSIS DOCUMENT THAT COULD BE |
| | REVIEWED FOR THE SMOKE CONTROL SYSTEM(S) APPLICABLE |
| | SEQUENCE OF OPERATION. |
| | |
| | SHEET M 8 WAS REVIEWED; HOWEVER, THE INFORMATION |
| | PROVIDED ON THAT SHEET DOES NOT PROVIDE CLEAR |
| | INDICATIONS IN A LOGICAL ORDER. |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAILED DOCUMENT FOR |
| | REVIEW. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |