2022-05-19 14:22:27PRIVATE PROVIDER MECHANICAL AUDIT
 PERMIT # 21071620
  
 THE KEYNOTES ARE MISSING ON SHEETS: AC-2.1; AC-3.0;
 AC-3.1; AC-4.0; AC-5.0;
 SHEETS AC-7.0, AC-7.3: NOTE PRINTED ON TOP OF ANOTHER
 NOTE MAKING IT IMPOSSIBLE TO READ EITHER NOTES.
 THE UNIT DRAWINGS SHOW MULTIPLE NUMBERS FOR THE CFM?S
 AT THE OUTSIDE AIR DUCT ENTERING THE UNITS. EXPLAIN WHY
 THERE ARE MORE THAN 1.
  
 SHEET AC-10.2: THE OCCUPANT LOAD FOR EACH USE OF SPACE
 MUST BE CALCULATED USING TABLE 403.3.1.1 AND NOT THE
 ARCHITECTS EGRESS OCCUPANT COUNT.
 SHEET AC-10.2: THE OCCUPANCY CATEGORY MUST MATCH THE
 OCCUPANCY CLASSIFICATION COLUMN IN FMC TABLE 403.3.1.1
  