| Plan Review Notes For Permit 21071620 |
| Permit Number |
21071620 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-19 14:22:27 | PRIVATE PROVIDER MECHANICAL AUDIT | | | PERMIT # 21071620 | | | | | | THE KEYNOTES ARE MISSING ON SHEETS: AC-2.1; AC-3.0; | | | AC-3.1; AC-4.0; AC-5.0; | | | SHEETS AC-7.0, AC-7.3: NOTE PRINTED ON TOP OF ANOTHER | | | NOTE MAKING IT IMPOSSIBLE TO READ EITHER NOTES. | | | THE UNIT DRAWINGS SHOW MULTIPLE NUMBERS FOR THE CFM?S | | | AT THE OUTSIDE AIR DUCT ENTERING THE UNITS. EXPLAIN WHY | | | THERE ARE MORE THAN 1. | | | | | | SHEET AC-10.2: THE OCCUPANT LOAD FOR EACH USE OF SPACE | | | MUST BE CALCULATED USING TABLE 403.3.1.1 AND NOT THE | | | ARCHITECTS EGRESS OCCUPANT COUNT. | | | SHEET AC-10.2: THE OCCUPANCY CATEGORY MUST MATCH THE | | | OCCUPANCY CLASSIFICATION COLUMN IN FMC TABLE 403.3.1.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|