| 2022-05-19 12:09:43 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E8.0 |
| | |
| | 1) MAIN BREAKERS TO MEET THE REQUIREMENTS OF 240.87 |
| | |
| | 240.87 ARC ENERGY REDUCTION. WHERE THE HIGHEST |
| | CONTINUOUS CURRENT TRIP SETTING FOR WHICH THE ACTUAL |
| | OVERCURRENT DEVICE |
| | INSTALLED IN A CIRCUIT BREAKER IS RATED OR CAN BE |
| | ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND (B) SHALL |
| | APPLY. |
| | |
| | 2) ALL SERVICES IN BUILDING SHALL HAVE DIRECTORIES |
| | INDICATING LOCATIONS OF ALL OTHER SERVICES PER |
| | 230.2.(E) |
| | |
| | 230.2(E) IDENTIFICATION. WHERE A BUILDING OR STRUCTURE |
| | IS SUPPLIED BY MORE THAN ONE SERVICE, OR ANY |
| | COMBINATION OF BRANCH |
| | CIRCUITS, FEEDERS, AND SERVICES, A PERMANENT PLAQUE OR |
| | DIRECTORY SHALL BE INSTALLED AT EACH SERVICE DISCONNECT |
| | LOCATION DENOTING |
| | ALL OTHER SERVICES, FEEDERS, AND BRANCH CIRCUITS |
| | SUPPLYING THAT BUILDING OR STRUCTURE AND THE AREA |
| | SERVED BY EACH. SEE 225.37. |
| | |
| | 3) FAULT CURRENT RATING CALCULATION SHALL BE SHOWN ON |
| | THE PLANS PER 110.24 PLEASE INDICATE ON THE PLANS HOW |
| | THE AIC RATING |
| | WAS CALCULATED SO THE FIELD LABEL REQUIRED BY THIS |
| | SECTION CAN BE COMPLETED. |
| | |
| | PAGE 8.1 |
| | |
| | 4) GENERATOR TO MEET THE REQUIREMENTS OF 700.3(F) |
| | |
| | 700.3(F) TEMPORARY SOURCE OF POWER FOR MAINTENANCE OR |
| | REPAIR OF THE ALTERNATE SOURCE OF POWER. IF THE |
| | EMERGENCY SYSTEM RELIES |
| | ON A SINGLE ALTERNATE SOURCE OF POWER, WHICH WILL BE |
| | DISABLED FOR MAINTENANCE OR REPAIR, THE EMERGENCY |
| | SYSTEM SHALL INCLUDE |
| | PERMANENT SWITCHING MEANS TO CONNECT A PORTABLE OR |
| | TEMPORARY ALTERNATE SOURCE OF POWER, WHICH SHALL BE |
| | AVAILABLE FOR THE |
| | DURATION OF THE MAINTENANCE OR REPAIR. |
| | |
| | 5) GENERATOR REQUIRES SEPARATE PLANS AND PERMIT. |
| | |
| | PAGE 8.2 |
| | |
| | 6) PHONE, DATA AND OTHER LOW VOLTAGW SYSTEMS REQUIRE |
| | SEPARATE PERMITS |
| | |
| | PAGE 8.3 |
| | |
| | 7) BDA REQUIRES SEPARATE PERMIT AND PLANS FOR REVIEW. |
| | |
| | PAGE 8.4 |
| | |
| | 8) FIRE ALARM REQUIRES A SEPARATE PERMIT AND PLANS FOR |
| | REVIEW. |
| | |