| 2021-11-01 15:00:58 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC B 1609, FROM PREVIOUS LIST: |
| | |
| | MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT |
| | OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE |
| | ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS |
| | IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE |
| | HUNG, AND SGD IN BOTH ZONES. |
| | |
| | 2ND REVIEW - THE SGD PRODUCT APPROVAL IS NOT MARKED. A |
| | NEW PRODUCT APPROVAL WAS UPLOADED NOTHING IS MARKED. |
| | |
| | FIXED WINDOW OPTION OK FOR THE MOST CURRENT DOCUMENT |
| | UPLOADED ON 10/21 BUT THE PRODUCT APPROVAL UPLOADED |
| | (NAMED NOA.PDF) IS INCOMPLETE; IT IS MISSING THE FIRST |
| | PAGE. THERE ARE TWO OTHER DOCUMENTS FOR A FIXED WINDOW |
| | NAMED "NOA FIXED.PDF" AND "PRODUCT APPROVAL - WINDOWS |
| | FIXED FL26095-R3.PDF" AND "PRODUCT APPROVAL.PDF". IT IS |
| | NOT CLEAR WHICH OF THE THREE IS PROPOSED; PLEASE ADVISE |
| | WHICH THREE SHOULD BE DELETED. IT APPEARS THAT |
| | "NOA.PDF" IS THE MOST CURRENT DOCUMENT AND THE OTHER |
| | THREE SHOULD BE DELETED, PLEASE CONFIRM. |
| | |
| | IT DOES NOT APPEAR A NEW PRODUCT APPROVAL FOR SINGLE |
| | HUNG WINDOW WAS NOT SUBMITTED. |
| | |
| | 2. SEE SHEET A1.0, ALUMINUM WINDOWS AND SGD ARE |
| | PROPOSED, BUT VINYL PRODUCT APPROVALS WERE SUBMITTED. |
| | REVISE. THE SCHEDULE DOES NOT APPEAR TO CORRELATE WITH |
| | THE PRODUCT APPROVAL SUBMITTED, PLEASE ADVISE WHICH |
| | PRODUCT APPROVALS SHOULD BE DELETED. THERE SHOULD BE |
| | THREE PRODUCT APPROVALS (SGD, FIXED, S/H) BUT 8 WERE |
| | UPLOADED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |