| 2021-08-04 14:27:25 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | WHERE ADDITION OR MODIFICATION IS MADE TO AN EXISTING | | | SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW | | | PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN | | | 200 PSI (13.8 BAR) FOR 2 HOURS. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|