Plan Review Notes
Plan Review Notes For Permit 21071453
Permit Number 21071453
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-08-06 14:15:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO INDICATIONS OF A FIRE HYDRANT WITHIN
 100' OF THE FDC.
  
 ALL PREVIOUS COMMUNICATIONS WITH THIS PROJECT NOTED THE
 REQUIREMENT.
  
 PLEASE PROVIDE FOR THE LOCATION OF THE FIRE HYDRANT.
  
  
 2) THE FIRE LINE UNDERGROUND SHALL BE INSTALLED,
 INSPECTED AND TESTED PER NFPA 24 AND MANUFACTURE'S
 SSPECIFICATIONS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  