| Plan Review Notes For Permit 21071453 |
| Permit Number |
21071453 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-06 14:15:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF A FIRE HYDRANT WITHIN | | | 100' OF THE FDC. | | | | | | ALL PREVIOUS COMMUNICATIONS WITH THIS PROJECT NOTED THE | | | REQUIREMENT. | | | | | | PLEASE PROVIDE FOR THE LOCATION OF THE FIRE HYDRANT. | | | | | | | | | 2) THE FIRE LINE UNDERGROUND SHALL BE INSTALLED, | | | INSPECTED AND TESTED PER NFPA 24 AND MANUFACTURE'S | | | SSPECIFICATIONS. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|