| 2021-10-12 13:06:06 | 2ND REVIEW FBC-2020 RES. BUILDING. |
| | PERMIT- 21071445 |
| | 10/12/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE RULE 9N-3 |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #5 FROM THE IST REVIEW HAS NOT BEEN ADDRESSED |
| | COMPLETELY. THE RESPONSIBLE DESIGN PROFESSIONAL IN |
| | CHARGE HAS APPROVED THE FLAT ROOF MATERIALS BUT NOT THE |
| | ROOF TILE, ADHESIVE AND UNDERLAYMENT. |
| | |
| | 5) THE ROOFING SUBMITTALS FOR THE PROPOSED BUILDING #6 |
| | UNDER PERMIT 20100736 WERE DEFERRED AND NOW MUST BE |
| | REVIEWED AND APPROVED BY THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE OF THE PROJECT. |
| | PLEASE PROVIDE SUBMITTALS BEARING THE APPROVAL STAMPS |
| | OF THE RESPONSIBLE DESIGN PROFESSIONAL. |
| | |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY |
| | SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE |
| | BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED |
| | AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF |
| | THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | NEW COMMENT: |
| | 1) PLEASE SEE THE LIMITATIONS OF USE NOTE #9 ON PAGE 4 |
| | OF THE BORAL TILESEAL UNDERLAYMENT NOA # 18-050203. |
| | BECAUSE THE UNDERLAYMENT IS NOT LISTED ON THE BORAL |
| | TILE NOA #19-1021.11, CALCULATIONS MUST BE PROVIDED TO |
| | SHOW COMPLIANCE WITH THE UPLIFT VALUES LISTED UNDER |
| | TABLE 1A OF THE FLORIDA HIGH WIND CONCRETE AND CLAY |
| | TILE INSTALLATION MANUAL. PLEASE NOTE THAT IN |
| | ACCORDANCE WITH THE TABLE THE INSTALLATION SHALL BE |
| | CAPABLE OF WITHSTANDING -115.5 FOR ALL ZONES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |