| 2021-07-30 15:11:12 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21071345 |
| | 7/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P101 & P201: THE KITCHEN SINK SHALL BE |
| | ACCESSIBLE IN COMPLIANCE WITH SECTIONS 212.3 AND 606.1 |
| | FBC ACC. PROVIDE THE FORWARD OR PARALLEL CLEAR FLOOR |
| | SPACE APPROACH DIAGRAM AND DIMENSION- 606.2, KNEE AND |
| | TOE CLEARANCES 306, AND HEIGHT OF THE SINK RIM OR |
| | COUNTER SURFACE FROM THE FINISHED FLOOR- SECTION 606.3. |
| | |
| | 2) P401: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | EWH-1- SECTION 502.1 FBC P. (MAY BE DEFERRED PER |
| | 107.3.4.1 WPB). |
| | |
| | 3) P401: SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE |
| | PAN WATER DETECTION DEVICE AND DETECTOR SHUTOFF- |
| | SECTION 504.7 FBC P AND SECTION 107.2.1 WPB. (MAY BE |
| | DEFERRED PER 107.3.4.1 WPB). |
| | |
| | 4) P401: SHOW THE SINK PAN DRAIN LINE TERMINATION |
| | LOCATION- 504.7.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |