| Notes |
| Date |
Text |
| 2021-10-05 16:13:21 | THE MEP SHEET HAS A SECTION HEADED AS AIR CONDITIONING | | | NOTES THAT INDICATES THAT THE MECHANICAL CONTRACTOR | | | WILL INSTALL A COMPLETE AND OPERATING A/C SYSTEM BUT | | | THE NOTE AT THE BOTTOM LEFT OF THE SHEET IS REVISED TO | | | INDICATE THE MECHANICAL SCOPE OF WORK IS TO REPLACE | | | EXISTING EXHAUST FANS AS PER PLANS. PLEASE CLEAR THIS | | | UP, IS THERE GOING TO BE NEW MECHANICAL SYSTEMS | | | INSTALLED? IF SO PLEASE PROVIDE THE MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS. IF NOT PLEASE REMOVE THE | | | AIR CONDITIONING NOTES SECTION. PROVIDE A COMPLETE | | | SCOPE OF WORK FOR THE MECHANICAL AND A MECHANICAL | | | SUBPERMIT WILL BE REQUIRED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|