| Plan Review Notes For Permit 21071307 |
| Permit Number |
21071307 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-11-15 07:37:16 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: REF. PRODUCT APPROVAL FL1850.3 AND THE SHUTTER | | | SCHEDULE FOR THE FOLLOWING COMMENTS: | | | | | | 1. ENTER ANCHOR TYPE ON PAGE 1 OF SCHEDULE. (SEE NOTE | | | AT BOTTOM OF SCHEDULE) | | | 2. TYPICAL SHUTTER INSTALLATION PER PRODUCT APPROVAL IS | | | VERTICAL. | | | 3. SHUTTER SPAN CANNOT BE LESS THAN THE VERTICAL | | | OPENING. | | | 4. CONNECTION TYPES ARE (A-TOP) (D-BOTTOM) AND | | | (H-BOTTOM OF OPENING #8). | | | 5. COMPLETE REQUIRED DATA FOR OPENING #8. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX. DO NOT | | | E-MAIL DOCUMENTS TO THE PLANS EXAMINER. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | |
|