| Date |
Text |
| 2021-09-22 15:31:52 | ALTERATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PLEASE SHOW THE INTERIOR STOREFRONT GLAZING WHICH IS |
| | TO BE USED AS A GUARD RAIL (2ND FLOOR) TO BE LAMINATED |
| | FBC 1015.2.1 GLAZING. |
| | WHERE GLASS IS USED TO PROVIDE A GUARD OR AS A PORTION |
| | OF THE GUARD SYSTEM, THE GUARD SHALL COMPLY WITH |
| | SECTION 2407. WHERE THE GLAZING PROVIDED DOES NOT MEET |
| | THE STRENGTH AND ATTACHMENT REQUIREMENTS OF SECTION |
| | 1607.8, COMPLYING GUARDS SHALL BE LOCATED ALONG GLAZED |
| | SIDES OF OPEN-SIDED WALKING SURFACES. FBC 2407.1 |
| | MATERIALS. |
| | GLASS USED IN A HANDRAIL, GUARDRAIL OR GUARD SECTION |
| | SHALL BE LAMINATED GLASS CONSTRUCTED OF FULLY TEMPERED |
| | OR HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH |
| | CATEGORY II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI |
| | Z97.1. |
| | |
| | 2) EXIT DOORS FOR OTHER UNITS HAVE BEEN REMOVED - TO |
| | ALLOW THE UNIT TO HAVE ONE EXIT DOOR PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION - PLEASE SHOW THE EXIT ACCESS ( |
| | DISTANCE FROM THE MOST REMOTE PLACE IN THE UNIT TO THE |
| | UNIT EXIT DOOR) TRAVEL DISTANCE1017.3 MEASUREMENT. EXIT |
| | ACCESS TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST |
| | REMOTE POINT OF EACH ROOM, AREA OR SPACE ALONG THE |
| | NATURAL AND UNOBSTRUCTED PATH OF HORIZONTAL AND |
| | VERTICAL EGRESS TRAVEL TO THE ENTRANCE TO AN EXIT. - |
| | PLEASE SEE FBC TABLE 1006.2.1SPACES WITH ONE EXIT OR |
| | EXIT ACCESS DOORWAY |
| | |
| | 3) PLEASE SHOW THE MEZZANINE AREA TO COMPLY WITH FBC |
| | 505.2.1 OR SHOW THE 2ND FLOOR (5TH FLOOR) EXIT PER FBC |
| | TABLE 1006.3.2 MINIMUM NUMBER OF EXITS OR ACCESS TO |
| | EXITS PER STORY |
| | |
| | 4TH FLOOR UNIT WILL REQUIRE THE FOLLOWING. |
| | THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | 4). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO |
| | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING |
| | TO PROJECTDOX ( [email protected] ) |
| | |
| | 5) A UNITY OF TITLE IS REQUIRED. |
| | |
| | |