| 2021-08-09 22:29:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SMOKE ALARMS SHOWN ON SEPARATE CIRCUITS. SMOKE |
| | ALARMS MUST BE TIED INTO LOCAL LIGHTING CIRCUIT PER FBC |
| | APENDIX J |
| | |
| | 2. PANEL B HAS 125AMP MAIN BREAKER WITH LOAD OF 128 |
| | AMPS. NEC 240 NEC 215 |
| | |
| | 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF TANKLESS |
| | WATER HEATER. WATER HEATER SHOWN AS 4KW ONLY. NEC |
| | 110.3B NEC 220 |
| | |
| | 4. SMOKE ALARMS OUTSIDE BEDROOMS MUST BE SMOKE/CARBON |
| | COMBOS. FBC 314 AND 315. |
| | |
| | 5. AFCI PROTECTION REQUIRED PER NEC 210.12A 210.12B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |