| 2021-08-25 10:41:22 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21071272 |
| | |
| | 1- ENGINEER OF RECORD TO REVISE THE WIND LOAD SUMMARY |
| | INFORMATION SUBMITTED: |
| | A)STRUCTURE IS LOCATED IN EXPOSURE "D" NOT EXPOSURE |
| | "C". REVISE AS REQUIRED. SEC. R301.2.1 FBC-RESIDENTIAL |
| | AND SEC. R301.2.1.4 FBC-RESIDENTIAL. |
| | |
| | 2- ENGINEER DRAWING DIGITALLY SIGNED BY DAN ROY A. |
| | BROWN P.E. HAS A SELF CERTIFIED DIGITAL SIGNATURE. A |
| | THIRD PARTY CERTIFICATION IS REQUIRED. FAC 61G15-23.004 |
| | |
| | ENGINEER CAN NOT SELF CERTIFY THE DIGITAL SIGNATURE. |
| | THIRD PARTY CERTIFICATION IS REQUIRED BY FAC |
| | 61G15-23.004. PLEASE UPLOAD DRAWINGS TO PROJECTDOX |
| | FOLDER WITH THE ENGINEER'S DIGITAL SIGNATURE. OR SUBMIT |
| | HARD COPIES WITH ORIGINAL SIGNATURE/SEAL. |
| | |
| | |
| | 61G15?23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY |
| | TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |