| 2021-08-24 13:42:32 | SIGNATURE REVIEW COMMENTS: | | | | | | 1- DRAWINGS SUBMITTED ELECTRONICALLY NEED TO HAVE THE | | | ORIGINAL SIGNATURE OF THE ENGINEER OF RECORD AS | | | REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING | | | PLANS/DOCUMENTS FOR PUBLIC RECORDS. | | | | | | 2- SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | | RECORDS. | | | | | | 3- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY | | | CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR | | | PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL | | | SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE. | | | | | | NOTE: PLANS/DOCUMENTS MAY BE SUBMITTED WITH A DIGITAL | | | SIGNATURE OR HARD COPIES WITH LICENSED DESIGN | | | PROFESSIONAL SEAL AND SIGNATURE MAY BE DROPPED (OR | | | MAILED) TO CITY HALL FOR RECORDS RETENTION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|