| 2021-11-15 18:26:37 | REBUILD DUPLEX (R3) THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21071231 |
| | |
| | |
| | NOTE: |
| | SECOND FLOOR FRAMING PLAN ON SHEET 4-4 IS MISSING THE |
| | SIZE OF THE FLOOR TRUSSES AND LIVE/DEAD LOADS DESIGN |
| | INFORMATION.. ENGINEER NEEDS TO SPECIFY THIS |
| | INFORMATION. |
| | |
| | |
| | 1- PERMIT APPLICATION STATES: "REMODEL TWO STORY |
| | BUILDING AS PER PLANS". PLANS SUBMITTED ARE FOR |
| | COMPLETE CONSTRUCTION OF A TWO STORY DUPLEX. NEED TO |
| | REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION TO |
| | SAY REBUILD TWO STORY DUPLEX. |
| | THE PERMIT TYPE WILL BE CHANGED FROM RESIDENTIAL |
| | REMODEL TO NEW RESIDENTIAL BUILDING PERMIT. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | SCOPE OF WORK ON PERMIT APPLICATION WAS NOT CHANGED. |
| | ALSO, SCOPE OF WORK ON SHEET 1-4 WAS REVISED TO SAY |
| | "REMODELING A 2-STORY CBS MULTIFAMILY RESIDENCE". THIS |
| | IS INCORRECT. THIS IS NOT A "REMODELING" PROJECT. THIS |
| | IS A REBUILD OR NEW CONSTRUCTION. REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- OK |
| | 3- OK |
| | 4- OK |
| | 5- OK |
| | 6- OK |
| | 7- OK |
| | 8- OK |
| | |
| | 9- STAIRWAY CONSTRUCTION: |
| | A) |
| | |
| | ORIGINAL COMMENT: |
| | B)PROVIDE NOSING DETAIL/SPECIFICATIONS AS REQUIRED BY |
| | SEC. R311.7.5.3 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | STAIR DETAIL ON SHEET 3-4 DOESN'T SHOW NOSING |
| | PROJECTION. IT SPECIFIES 3/4" NOSING BUT THE DETAIL |
| | DOESN'T SHOW THE 3/4" PROJECTION. REVISE AS REQUIRED. |
| | SHOW THE NOSING PROJECTION. |
| | |
| | C) OK. |
| | D) OK. |
| | |
| | E) DEFERRED SUBMITTAL: AFTER THE PERMIT IS ISSUED NEED |
| | TO SUBMIT HANDRAIL AND GUARDRAIL SHOP DRAWINGS APPROVED |
| | BY ENGINEER OF RECORD AS DEFERRED SUBMITTAL. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 10- OK |
| | 11- OK. |
| | 12-OK. |
| | 13-OK |
| | 14-OK |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |